ZENNER zelsius C5 IUF User Manual

Page 7

Advertising
background image

7

Notes to installation of the ball valves

Mount ball valves up- and downstream of the
meter.

Mount a ball valve with bore M10x1 for direct
sensors in the supply. This is required for the
installation of the supply sensor.

For symmetrical temperature sensor instal-
lation, mount an identical ball valve in the
return. This one is used for mounting the
return sensor.

Mounting heating-/cooling energy meter

Flush the system thoroughly before installing
the heating-/cooling energy meter.

Close valves and release pressure.

Dismount the existing flow sensor or meter
blank.

Use only new and flawless sealing material
and check the seal face for damage.

Install the new flow sensor according to the
correct flow direction and installation position.

Turn heat computer to desired reading posi-
tion.

Mounting temperatur sensors

The installation of the temperature sensors
should be preferably symmetrical and direct
installation.

Do not remove the return sensor if already
mounted on the VMU. This is also valid for
all the safety seals which are mounted on the
device as a standard.

Sensors are colour-coded (red= hot; blue=cold).

The connecting cables may not be buckled,
extended or shortened.

The seal at the sensor installation point on the
measuring capsule may not be damaged.

Remove locking screw and seal at the ball
valve completely, if existing.

Attach the O-ring to the installation aid (the
2nd O-ring is only a spare O-ring). Using the
installation aid, insert the O-ring into the
installation point according to DIN EN 1434
with a slight circular motion.

Using the other end of the installation aid
bring the O-ring into the correct position.

Insert the 2 halves of the plastic connector
into the sensor’s three notches (crimps) and
press them together.

Use the installation aid as positioning aid.

Insert the temperature sensor into the installa-
tion point and screw it in tightly until the dead
stop of the seal on the 12-point is reached
(mounting torque 3-5 Nm).

The temperature sensor installation point
which is optionnally integrated in the flow
sensor must be secured.

Secure the sensor after installation against
unauthorised removal with appropriate sealing
(available as a sealing set)!

Installation DF-adapter