Pellet Vent Type

Must be 4" diameter Type "L"(except for masonry fireplace installations) - or - connect the
vent to a factory built type "A" chimney. All vent joints (including adapters, elbows, etc…)
must be sealed with 500° F. RTV silicone.

Installing the Pellet Vent

Seal each vent section (including
adapters, elbows, etc...) by
injecting a liberal amount of 500°
F. RTV silicone into the gap
between sections.

500° F. RTV

Silicone

Horizontal sections must have a 1/4" rise every 12" of travel.

Pellet vent connections must be sealed airtight with 500° F. RTV silicone and screwed
together with at least three sheet metal screws.

Pellet Vent Termination (See the illustration below)

Must have an approved cap (to prevent water from entering) or a 45° downturn.

If the termination is located on a windy side of the house, an approved house shield is
recommended to prevent soot from building up on the side of the house.

Must not be located where it will become plugged by snow or other material.

Horizontal terminations must protrude 12" from the wall, verticall terminations require 24".

H

G

A

D

F

NOTE: Measure clearances to the nearest edge of the exhaust hood.

A

E

B

C

F

X

A

Minimum 4' clearance below or beside any door or window that opens

B

Minimum 1' clearance above any door or window that opens

C

Minimum 2' clearance from any adjacent building

D

Minimum 7' clearance above any grade when adjacent to public walkways
NOTE: Vent may not terminate in covered walkway or breezeway.

E

Minimum 2' clearance above any grass, plants, or other combustible materials

F

Minimum 3' clearance from any forced air intake of any other appliance

G

Minimum 2' clearance below eaves or overhangs

H

Minimum 1' clearance horizontally from combustible wall

X

Must be a minimum of 2' above the roof