1-2

BE1-50/51B-219/-226 General Information

9252000981 Rev H

type curves, and instantaneous or integrating reset characteristics. Switch location and description is
provided in Section 2.

Advantages

BE1-50/51B-219 and BE1-50/51B-226 overcurrent relays have many advantages over other overcurrent
relays. The primary advantages are.

 Time characteristics are defined by equations and graphs

 Field selectable time characteristics

 Very low burden extends the linear range of the CTs

 Self powered from the sensed current

 Continuous

automatic

calibration

BE1-50/51B-219 and BE1-50/51B-226 overcurrent relays may be tested without removing the relay from
the case. Shorting contacts are provided for all current inputs when the connection plugs or relay chassis
is removed from the relay case.

SPECIFICATIONS

BE1-50/51B-219 and BE1-50/51B-226 electrical and physical specifications are listed in the following
paragraphs.

Current Sensing Input

BE1-50/51B-219

Continuous Current:

14 Aac

One Second Rating:

400 Aac

BE1-50/51B-226

Continuous Current:

2.8 Aac

One Second Rating:

80 Aac

Time Overcurrent (51) Element

Setting the TIME PICKUP control at the minimum pickup setting places the relay in the most sensitive
state and may be used as a safety setting.

BE1-50/51B-219 Pickup

Setting Range:

0.5 to 15.9 Aac

Setting Increment:

0.1 Aac

Accuracy:

±2%, ±25 milliamperes at or above 0.5 ampere setting

BE1-50/51B-226 Pickup

Setting Range:

0.1 to 3.18 Aac

Setting Increment:

0.02 Aac

Accuracy:

±2%, ±5 milliamperes at or above 0.1 ampere setting

Dropout

Dropout occurs at 95% of pickup value.

Timing Range

0.0 to 9.9 seconds in 0.1 second steps.

Timing Accuracy

The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap
and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that
is the sum of ±2%, ±25 milliamperes for the BE1-50/51B-219 and ±2%, ±5 milliamperes for the BE1-
50/51B-226.