Basler Electric BE3-49R-6 Inputs User Manual

Instructions, Be3-49r - 6 inputs

Advertising
background image

www.basler.com

+1 618.654.2341 (USA)

[email protected]

Model

BE3-49R - 6 Inputs

INTRODUCTION

Six-input BE3 temperature relays use resistance
temperature detectors (RTDs) to monitor remote
temperatures. When any of six monitored temperatures
exceeds a preset limit, the corresponding LED indicator
lights, the TRIP LED lights, and the relay output operates.
BE3 temperature relays are available for use with 10

copper or 100

Ω platinum RTDs.

SPECIFICATIONS

Operating Power

All units require external operating power.

Nominal Voltage:

120 Vac, ±25%, 45 to 65 Hz, 2 VA

240 Vac, ±25%, 45 to 65 Hz, 2 VA

24 Vdc, ±20%, galvanically
isolated, <3 W

RTD Inputs

The RTD inputs accommodate two- or three-wire RTDs.
Depending on the style number of the relay, the RTD inputs
accept either 10

Ω copper or 100 Ω platinum RTDs.

Style 5J5X1:

10

Ω copper RTDs

Style 5K5X1:

100

Ω platinum RTDs

The temperature measurement range of each input is 0 to
200

°C.

Metering Output

Range:

0 to 1 mAdc

Burden:

5 k

Ω maximum

Setpoints

Range:

50 to 100% (

±3%) of input

temperature range

Repeatability:

Greater than 0.5% of full span

Differential:

Fixed at 2%

Outputs

Relay Type:

S.P.D.T.

AC Rating:

250 V, 5 A, non-resistive,
1200 VA

DC Rating:

125 V, 1 A, resistive, 120 W

Mechanical Life:

5 million operations

Temperature

Operating Temperature: 0°C (32°F) to 60°C (140°F)

Functional Temperature: –25°C (–13°F) to 70°C (158°F)

Storage Temperature:

–40°C (–40°F) to 85°C (185°F)

Temperature Coefficient: 0.03% per °C (300 ppm/°C)

Humidity

Relative Humidity:

95% non-condensing

Physical

Mounting:

DIN rail 1.38” by 0.29” (35 mm by
7.5 mm)

Case:

Complies with IEC 529, DIN
40050, BS 5490

Case Material:

Complies with UL 94VO

Weight:

1.32 lb (0.59 kg)

Size:

3.94” wide (100 mm)

Agency

cULus listed to UL 508 and CSA C22.2 No. 14

CE compliant

GOST-R certified per the relevant standards of Gosstandart
of Russia

OPERATION

Six temperatures are monitored through RTDs connected to
the BE3 temperature relay. RTD connections are labeled A,
B, C, D, E, and F. One front-panel control labeled SET is
used to adjust the trip level for all six RTDs. The setpoint is
adjustable from 50 to 100% (

±3%) of the RTD temperature

range. When any RTD temperature exceeds the setpoint,
the TRIP LED lights, and the relay output energizes. Each
RTD has a corresponding LED to identify which RTD has
exceeded the temperature setpoint. For example, if the
temperature of RTDs B and C exceeds the trip level, the B,
C, and TRIP LEDs light and the relay output energizes. A
green LED labeled AUX indicates the power supply status.

INSTALLATION

BE3 temperature relays are designed for mounting on
standard DIN rails that comply with DIN-EN 50022.

Mounting involves hooking the top edge of the cutout on the
base of the case over one edge of the DIN rail. The opposite
side of the cutout containing the release clip is then pushed
over the opposite side of the DIN rail. To remove or
reposition the relay, lever the release clip and move the
relay as required. BE3 relays should be installed in a dry,
vibration-free location where the ambient temperature does
not exceed the operating temperature range. Connections to
the relay should be made using wire that meets applicable
codes and is properly sized for the application. Figure 1
illustrates the terminal connections for the BE3-49R
temperature relay.

A burden resistor must be installed across all unused RTD
inputs that are not connected to an actual RTD. For units
with style number 5JXXX, it is suggested that a 10

Ω resistor

be connected across any unused RTD inputs. For units with
style number 5JXXX, it is suggested that a 100

Ω resistor be

connected across any unused RTD inputs. The minimum
power rating for the burden resistors is ¼ W.

Publication

9320500991