Instructions – Basler Electric BE3-49R-6 Inputs User Manual

Page 2

Advertising
background image

CALIBRATION

Proper calibration requires a precision decade resistance
box with 1% accuracy or better. While calibrating the relay,
burden resistors must be connected across the remaining,
open RTD inputs. A temperature and resistance cross-
reference table for your RTDs is also needed. Use the
following procedure to calibrate your relay.

1.

Adjust the SET control fully counterclockwise.

2.

Connect the decade resistance box to RTD input A and
connect a 10

Ω (style 5JXXX) or 100 Ω (style 5KXXX)

burden resistor across the remaining RTD inputs. The
burden resistor power rating should be ¼ W or greater.
Apply nominal external operating power to the relay.

3.

Set the decade resistance box at the value that
corresponds to the desired temperature setpoint.

4.

Slowly adjust the SET control clockwise until the A and
TRIP LEDs light and the output relay energizes.

MAINTENANCE

BE3 relays are solid-state devices that require no
maintenance. In the event that your relay requires repair,
contact Basler Electric, Highland, IL, USA for return
authorization.

ORDERING INFORMATION

Figure 2 shows the BE3 temperature relay style chart.

FIGURES

Figure 1. BE3-49R - 6 Input Connections

Figure 2. BE3-49R - 6 Input Style Number Identification Chart

Publication

9320500991

Revision

D

Instructions

Date

03/14

Page

2 of 2

Advertising