INTRODUCTION

The BE300PM static voltage regulator regulates voltage on

a 50- or 60-Hz generator with a brushless exciter and a

permanent magnet generator (PMG) excitation system.

ELECTRICAL SPECIFICATIONS

Output Power

Maximum Continuous: 3 Adc at 63 Vdc (190 W)

One-Minute Forcing:

5 Adc at 100 Vdc (500 W) with

240 Vac power input

Exciter Field DC Resistance

Minimum:

15 Ω

Input Power

Range:

171 to 264 Vac, single-phase

Frequency:

250 to 300 Hz, ±10%

Burden:

500 VA

Sensing Input

Range:

171 to 264 Vac, single-phase

Frequency:

50 to 75 Hz

Fuse

Bussmann GDC-4A or equivalent

Rating:

4 Aac, 250 Vac

Type:

Glass tube, 5 x 20 mm, time delay

Voltage Adjustment Range

171 to 264 Vac
Regulation Accuracy

Better than ±1.0%, no-load to full-load
EMI Suppression

Internal electromagnetic interference (EMI) filtering
Voltage Buildup

Automatic voltage buildup occurs for residual generator

voltages as low as 10 Vac.
Power Dissipation

8 W maximum

PHYSICAL SPECIFICATIONS

Temperature

Operating:

–40 to 60°C (–40 to 140°F)

Storage:

–40 to 85°C (–40 to 185°F)

Vibration

20 to 60 Hz with 0.035” displacement

1,000,000 cycles @ 30 Hz in all planes
Shock

Withstands 15 G in each of three perpendicular planes.
Moisture and Humidity
Tested per MIL-STD-705B, Method 711-1C
Salt Fog
Tested per ASTM B117-73
Weight

184 g (6.5 oz) net

Terminal Type
¼ inch male quick connect with insulating barrier
Agency Certification

Standard CSA-C22.2 No. 0 and 14

File LR 23131

OVEREXCITATION PROTECTION

If the exciter field voltage exceeds 85 to 90 Vdc, the

BE300PM automatically removes field power after a time

delay. This delay is inversely proportional to the field

voltage.
When field power is removed due to overexcitation, the

BE300PM will not reset or return to operation until the

generator output is interrupted.

CONTROLS

BE300PM controls consist of jumpers and screwdriver

adjusted potentiometers.
Potentiometer Controls
BE300PM potentiometer controls are accessible through

the controller front panel and are shown in Figure 1.
VOLT Control
This control raises and lowers the generator output voltage.
STAB Control
This control adjusts the stability by increasing and

decreasing the response time of the BE300PM.
U/F Control
This control adjusts the corner frequency point of the

BE300PM frequency compensation characteristic.
Optional Remote Voltage Adjust Rheostat
If remote adjustment of the generator output is desired, the

Voltage Adjust Rheostat jumper must be replaced with a

user-supplied rheostat. A 2,000 ohm, ½ watt rheostat will

provide ±10% voltage adjustment. For ±5% voltage

adjustment, use a 1,000 ohm, ½ watt rheostat. Figure

2

shows the proper remote rheostat connections. Refer to

Operating Procedures for instructions on setting up the

remote rheostat.
Jumpers
Two jumpers control BE300PM operation: the Corner

Frequency jumper and the Voltage Adjust Rheostat jumper.

These jumpers are shown in Figure 3.
Corner Frequency Jumper
BE300PM controllers are delivered with the nominal corner

frequency preset to 58 hertz in the 60 hertz mode. For 50

hertz operation, and a nominal corner frequency of 48

hertz, the Corner Frequency jumper must be moved to the

50 Hz terminal.
Voltage Adjust Rheostat Jumper
BE300PM controllers are delivered with the Voltage Adjust

Rheostat jumper connected across terminals 6 and 7. This

enables adjustment of the generator output voltage through