Instructions, Caution – Basler Electric BE300PM User Manual

Page 2

Advertising
background image

the controller’s internal Voltage Control potentiometer.

Clockwise rotation of the Voltage Control potentiometer

increases the generator voltage.

INPUT POWER

Power for the exciter field and BE300PM is derived from

the permanent magnet generator (PMG) output. The

acceptable power input range is 171 to 264 Vac. Connect

the PMG input power wiring to terminals 3 and E3/4.

Typical connections are shown in Figure

2.

SENSING INPUT

BE300PM sensing is derived from the generator output.

The acceptable input range is 171 to 264 Vac. Connect the

generator sensing wiring to terminals E1 and E3/4. Typical

connections are shown in Figure

2.

EXCITER FIELD POWER CIRCUIT

Controller terminal F+ is connected to the brushless exciter

field positive terminal and controller terminal F– is

connected to the brushless exciter field negative terminal.

Caution

The exciter field dc resistance must be no less than

15 ohms.

If the exciter field dc resistance is less than 15 ohms and

the full-load field current does not exceed the maximum

continuous current rating of the controller, a resistor of

sufficient wattage must be added in series with the field to

increase the total resistance to ≥ 15 ohms.

STABILITY ADJUST

The stability adjust potentiometer allows for tuning of the

regulator to optimize generator voltage settling time.

Achieving the desired voltage stability on larger machines

may not be possible with adjustment of the Stability Adjust

potentiometer alone. If this occurs, cutting both stability

circuit-selection jumpers (see Figure 4) will allow

adjustment to the desired stability.

FREQUENCY COMPENSATION

The frequency compensation feature improves system load

pickup performance by restraining voltage recovery until

the frequency has also started to recover. Figure 5

illustrates the underfrequency characteristics of the

BE300PM.
The corner frequency range is set for 50 hertz or 60 hertz

by connecting the Corner Frequency jumper to the

appropriate terminal. The adjustable range is 54 to 61 hertz

in 60 Hz operation and 45 to 51 hertz in 50 Hz operation.

Refer to Controls, Jumpers for details on selecting the

corner frequency range.
The corner frequency setting is adjusted by the

Underfrequency control (potentiometer). Clockwise rotation

of the Underfrequency control increases the corner

frequency and counterclockwise rotation decreases the

corner frequency. If user adjustment of the factory-set

Underfrequency potentiometer is desired, follow the

Preliminary Setup and System Startup procedures.

INSTALLATION

Mounting
The BE300PM controller may be mounted on the generator

in any convenient position. Figure 6 shows the mounting

dimensions. Dimensions are shown in inches with

millimeters in parenthesis.
The recommended mounting hardware is two #8 or M4

screws tightened to a torque of 9 inch-pounds (1 newton

meter). Nylon-lined locking nuts are recommended when

installing the controller with loose hardware.
Connections
BE300PM controller terminals consist of quarter-inch,

quick-connect tabs.
Figure

2 shows typical connections for the BE300PM

controller.

OPERATING PROCEDURES

The following procedures can be used when adjusting the

BE300PM controller. Symptoms caused by certain

generator system problems or a faulty controller are

included along with suggested remedies.

Caution

Meggers and high-potential test equipment must not be

used. Use of such equipment may damage the

semiconductors contained in the controller.

Preliminary Setup
Complete the following steps before proceeding with

system startup.
1. Verify that the BE300PM specifications conform to the

requirements of the generator system.

2. Ensure that the controller jumpers are positioned as

follows:
a. If a remote voltage adjust rheostat will not be

used, ensure that the Voltage Adjust Rheostat

jumper is connected across terminals 6 and 7.

b. If a 54 to 61 hertz corner frequency is desired,

connect the Corner Frequency jumper to the 60

Hz terminal. If a 45 to 51 hertz corner frequency is

desired, connect the Corner Frequency jumper to

the 50 Hz terminal. The corner frequency is fine-

tuned in the System Startup procedure.

3. Ensure that the connections between the generator

system and the controller are correct.

4. Set the BE300PM Voltage control fully

counterclockwise and the remote voltage adjust

rheostat (if used) to the center position.

5. Adjust the BE300PM stability control fully clockwise.

This provides the most stability and the slowest

response.

6. If user adjustment of the Underfrequency control is

required, start with the potentiometer adjusted to the
fully counterclockwise position. Then, slowly adjust the
potentiometer clockwise to set.

Publication

9166800894

Revision

B

Instructions

Date

01/13

Page

2 of 4

For terms of service relating to this product and software, see the Commercial Terms of Products and Services document available at

www.basler.com/terms

.

Advertising