BECKHOFF BK51x0 User Manual

Page 3

Advertising
background image

BECKHOFF New Automation Technology

page 3/4

Update info CANopen version 3 to version 4.01

2002-04-30

Advantage: Uniform and manufacturer independent LED behaviour

Effects when using new bus couplers in existing networks: Optical diagnosis in error case

has changed minimally. No change in normal operation.

3.

Object Dictionary

3.1

Identity Object now supported

New: The new CANopen Identity Object 0x1018 is now supported. It provides the following

information about the device:

Sub index 1: Vendor ID. Beckhoff has the Vendor ID 2.

Sub index 2: Product Code. BK5120: 0x11400; BK5110: 0x113F6; LC5100: 0x113EC;
IPwxyz-B510: 0x2wxyz; IL2301-B510: 0x2008FD.

Sub index 3: Revision Number

Sub index 4: Production date; Low Word, High Byte: Calendar week (dec), Low Byte:
Calendar year

Advantage: Additional information about the device is provided manufacturer independently.

Effects when using new bus couplers in existing networks: none

3.2

0x100E: Guarding-Identifier now Read-Only

New: The default identifier for the Guarding and Heartbeat Protocol may not be changed any

more.

Advantage: Clear assignment of the corresponding CAN Frames to the node addresses.

Effects when using new bus couplers in existing networks: Only, if Guarding identifier was

changed.

3.3

Object 0x1004 removed

New: In CANopen Version 4.0 Object 0x1004 (Number of PDOs) is not supported any more,

as it did not provide valuable information.

Advantage:

reduced memory usage.

Effects when using new bus couplers in existing networks: Only, if number of PDOs was

derived from object 0x1004.

3.4

Time-Out at SYNC monitoring extended

New: The watchdog for the SNYC monitoring is now set to the 1,5-fold of the value in Object

0x1006.

Advantage: Now the actually intended SYNC Interval can be written to Object 0x1006.

Effects when using new bus couplers in existing networks: none

4.

Network Management

4.1

Boot-Up message now uses guarding identifier

New: The boot-up message, that Beckhoff had introduced, in CANopen version 4 now has

been defined manufacturer independently. Instead of an Emergency message without
data now a Guarding telegram with one data byte (0) is sent.