Specifications, Terminals and connections, Low voltage – Boyertown nrgMax Universal Oil Control V4.0 User Manual

Page 4: Line voltage, Burner connections, Status led flashing patterns, 1sec 1 sec 1 sec

Advertising
background image

SPECIFICATIONS

Electrical Ratings:

Power Requirements:

Voltage: 24Vac, 50/60 Hz.

Current: 4 VA at 24 Vac.

PTC Fuse (resettable) trips at 4.5A

Contact Ratings:

Circulating Fan: 15A Full Load, 30A Locked
Rotor at 115 Vac (includes optional EAC
load).

Burner: 5.8 A Continuous Load (7.4A with
interrupted ignition)

Settings: Standard Configuration

Heating:

Blower On Delay: 30 or 75 seconds, field-
adjustable

Blower Off Delay (BOD): 90, 120, 150, 180
seconds, field-adjustable.

Timing Tolerance: less than 1 second

Environmental Ratings:

Temperature: -40 to +150° F [-40° to +66° C].

Humidity: 95% maximum, non-condensing.

Terminals and Connections:

Low Voltage:

Thermostat:

G:

Blower On

W:

Call for heat (0.08A load)

R:

24VAC out to thermostat

Y1:

Cooling, Stage 1

C:

24Vac common

W2:

Heating, Stage1

Y2:

Cooling, Stage2

Yx:

Dummy terminal, no connection

O:

Heat pump reversing valve

DH:

Dehumidification

CLASS 2 TRANSFORMER 50VA Max (overload
protected)

X:

24VAC

C

24VAC Common

16-PIN ECM Connector: Convenient interface
between 10-position thermostat, DIP-switches and
ECM motors.

Option Jumpers: Selectable Options:

F1 Reserved

F2 Enhanced PSC Mode

F3 Extended Blower On Delay (75 Sec)

Line Voltage:

Unused: No connection (2 terminals)

L1:

120VAC 60Hz, 1ph, 15 A mp (Max) supply

N:

120VAC Neutral supply

Neutrals: Connection points for loads, tied internally
to N (6 terminals)

120VAC : L1 supply to accessories, continuously
powered (3 terminals)

Cont.

120VAC to Continuous speed of blower.

Normally energized, it is de-energized whenever
Cool or Heat terminals are energized

EAC:

120VAC to Electronic Air Cleaner.

Energized along with Cool or Heat terminals

Heat:

120VAC 15A, 1HP blower speed.

Cool:

120VAC 15A, 1HP blower speed

H:

120VAC 1A to Humidifier. Powered by

burner motor feedback (Pins 7-8 on 9-pin burner
connector).

Burner Connections:

9-PIN AMP Connector:

(MATES WITH TYCO PART #350720)

1)

Safety Limit string (return)

2)

120VAC to Oil Burner (high-limit protected)

3)

Burner T-T (internally connected to Pin 6)

4)

Neutral (internally connected to Pin5 and N)

5)

Neutral (internally connected to Pin 4 and N)

6)

Burner T-T (internally connected to Pin 3)

7)

Burner Motor (internally connected to Pin 8)

8)

Burner Motor (internally connected to Pin 7)

9)

120VAC to Safety Limit string. Normally off,
energized on call for heat by Relay K1

Edge Connector (Alternate, 6 conductor) mates with
Molex 09-01-6061.

Motor: Burner Motor

Limit: 120VAC to Safety Limit string. Normally
off, energized on call for heat by Relay K1

Limit: Safety Limit string (return)

L1: 120VAC to Oil Burner (high-limit
protected)

120V: 120VAC Continuous (not limit protected)

Status LED Flashing Patterns

nrgMAX

(division of Bob Tonner Applied Research Inc)

Pickering, ON, 289-800-7131 www.nrgmax.ca

1

sec

1

sec

1

sec

Standby

Heating

Cooling

Limit

Limit reset

No Burner