Contemporary Control Systems BACnet Cube I/O BMT-DO4 User Manual

Page 2

Advertising
background image

METZ CONNECT | Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Distributed by RIA CONNECT GmbH and BTR NETCOM GmbH
Mounting instruction see www.metz-connect.com

2

1

6. Mounting

Power down the equipment

Mount the module on standard rail (TH35 per IEC 60715 in
junction boxes and/or on distribution panels).
Installation

Electric installation and device termination shall be done by qua-

lified persons only, by respecting all applicable

specifications and regulations.

Plug in the terminal block for bus connection

4

3

5 mm

5

6

The module can be aligned without interspace. Use the jumper
plug to connect bus and supply voltage when the modules are
mounted in series.
The maximum quantity of modules connected in line is limited

to 15 or to a maximum power consumption of 2 Amps (AC or

DC) per connection to the power supply. For any similar block

of additional modules a separate connection to the power

supply is mandatory.

Connect the cable for bus supply

Mounting in series

8. Connection examples

41

42

44

31

32

34

ERROR

24V

1
A

X10

0

A-

B+

GND

+24 V

A-

B+

GND

+24 V

24V

14

11

12

24

21

22

BUSY

X1

BMT-DO4

BACnet MS/TP

N

L

M

1

2

3

4

7. Network adress and Bit rate setting

Configuration Switches

Hexadecimal Switches x10, x1 define the Network Address

(00 - F9; e.g. F9h = 15x16+9 = 249d) and Baud rate (FA – FF).

• Turn Switch x10 to E (Device is temporaryly configured as Slave)

• Turn Switch x1 to A – F to select Baud rate

• Turn Switch x10 to F, wait 1 second

• Red and green LEDs are blinking when Baud rate ist stored in

EEPROM

• Turn Switch x10 to select Network Address

• Turn Switch x1 to select Network Address
MS/TP Master if using Network Address 0x00 … Max_Master,
MS/TP Slave if using Network Address Max_Master + 1 … 0xF9.

Factory setting: 9600 Bit/s

Adress switch x10

F

F

F

F

F

F

Adress switch x1

A

B

C

D

E

F

Bit rate (Bit/s)

9600 19200 38400 57600 76800 115200

9. Software Description

Device Object

Property

Remark / Value

RW

Object_Identifier

device, default instance: 421000 + Network-Address

RW-E

Object_Name

max. 63 Bytes,
default “BMT-DO4_” + Network-Address (Hexadecimal)

RW-E

Object_Type

DEVICE (8)

R

System_Status

OPERATIONAL (0)

R

Vendor_Name

“BTR Netcom GmbH”

R

Vendor_Identifier

421

R

Model_Name

“BMT-DO4”

R

Description

max. 127 Bytes, default “”

RW-E

Location

max. 63 Bytes, default “”

RW-E

Firmware_Revision

“1.2”

R

Application_Software_Version

“1.0”

R

Protocol_Version

1

R

Protocol_Revision

12

R

Protocol_Services_Supported

read-property, write-property, subscribe-cov, who-has, who-is, device-communication-
control, reinitialize-device

R

Protocol_Object_Types_Supported

DEVICE, BINARY_OUTPUT, ANALOG_VALUE

R

Object_List [6]

device, binary-output 1…4, analog-value 1

R

Max_APDU_Length_Accepted

480

R

Segmentation_Supported

NO_SEGMENTATION (3)

R

APDU_Timeout

10000

R

Number_Of_APDU_Retries

3

R

Device_Address_Binding

-

R

Database_Revision

0

R

Max_Master

0…127, default 127

RW-E

Max_Info_Frames

1…255, default 1

RW-E

Active_COV_Subscriptions

max. 6 Subscriptions, for binary-output 1…4,
Confirmed / Unconfirmed, Lifetime = 0…65535 sec.

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash