Continuation Software Description

Binary Output Object 1…4

Property

Remark / Value

RW

Object_Identifier

binary-output, instance 1 … 4

R

Object_Type

BINARY_OUTPUT (4)

R

Object_Name

max. 42 Bytes, default “Relay 1” … “Relay 4”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

NULL (write only) / INACTIVE (0) / ACTIVE (1)

RW

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN:

0 = Switch A (Auto)

1 = Switch 0 (Off) or 1 (On)

OUT_OF_SERVICE: 0 / 1

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0) / TRUE (1)

RW

Polarity

NORMAL (0) / REVERSE (1)

RW-E

Priority_Array [16]

NULL / INACTIVE (0) / ACTIVE (1)

R

Relinquish_Default

INACTIVE (0)

R

Inactive_Text

max. 20 Bytes, default “Off”

RW-E

Active_Text

max. 20 Bytes, default “On”

RW-E

Notification_Class

Unsubscribed UnconfirmedCOVNotification
0: no COV notification, default,
1: local broadcast,
2: global broadcast

RW-E

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

Function Table for Binary Output

Out_Of_Service

Polarity

Switch

Priority_Array

Present_Value

Binary Output

OVER RIDDEN

OUT_OF_SERVICE

0

0

A

NULL / 0 / 1

0 / 0 / 1

0 / 0 / 1

0

0

0

0

0
1

NULL / 0 / 1
NULL / 0 / 1

0
1

0
1

1

0

0

1

A

NULL / 0 / 1

0 / 0 / 1

1 / 1 / 0

0

0

0

1

0
1

NULL / 0 / 1
NULL / 0 / 1

1
0

0
1

1

0

1

0

A

NULL / 0 / 1

0 / 0 / 1

0

0

1

1

0

0
1

NULL / 0 / 1
NULL / 0 / 1

0 / 0 / 1
0 / 0 / 1

0
1

0

1

1

1

A

NULL / 0 / 1

0 / 0 / 1

1

0

1

1

1

0
1

NULL / 0 / 1
NULL / 0 / 1

0 / 0 / 1
0 / 0 / 1

0
1

0

1

Continuation Software Description

Analog Value Object 1

Property

Remark / Value

RW

Object_Identifier

analog-value, instance 1

R

Object_Type

ANALOG_VALUE (2)

R

Object_Name

max. 42 Bytes, default “Watchdog Time”

RW-E

Description

max. 84 Bytes, default “”

RW-E

Present_Value

Time Constant of Watchdog Timer,
0: Watchdog is inactive, Maximum: 655.34 seconds

RW-E

Status_Flags

IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0

R

Event_State

NORMAL (0)

R

Out_Of_Service

FALSE (0)

R

Units

seconds (73)

R

R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash

The Watchdog Timer resets Present_Value of all output objects to Relinquish_Default, if BACnet communication fails permanently. The timer is re-
started, when a BACnet message with an APDU is received.
When the timer times out, the priority arrays of all output objects are completely cleared to NULL.