Troubleshooting – Daktronics E SERIES User Manual

Page 16

Advertising
background image

TROUBLESHOTOTING

17

SYMpTOM

pOSSIBlE CAUSE

CORRECTIVE ACTION

Controller is not on

Power failure

Check incoming power to controller.

Key switch not turned on

Turn key switch to ON.

Password will not work

Forgot password

Have administrator level user

log in and create new user

with new password.

Vortek hoist will not move

when commanded

EMERGENCY STOP button pressed

Check all EMERGENCY STOP

buttons.

Hoist is faulted

Check fault codes by pressing the

error bar at the bottom of the screen.

Reset hoist using reset button.

Hoist has reached limit

Check limit, readjust as necessary.

Overload/Underload fault condition

Check settings and reset parameters

if required. Refer to hoist setup

and debug screen.

Preset information not set correctly or

there is no hoist speed set

Set preset information and/or hoist

speed. Refer to hoist setup and

debug screen.

Touchscreen not operating

Dirty touchscreen

Clean touchscreen with window

cleaner and soft cloth. Cycle power

to restart PLC and HMI.

No network communications

Main high voltage power turned off

to hoists

Check to make sure high voltage to

hoists is turned on.

Low voltage connector not connected

to hoist

Check connection of low voltage wire

way connector to hoist.

E-Stop circuit not resetting

24 V DC power problem

Open controller and check for green

light on 24 V DC power supply.

Check 24 V DC power fuse.

07

TROUBLESHOOTING