User Instructions Logix 510si - LGENIM0510-0

2 12/13

4 SPECIFICATIONS

Table 1: Input Signal

Input Signal Range

4 - 20 mA

Compliance Voltage

6 VDC

Voltage Supply (maximum)

30 VDC

Minimum Required Operating
Current

3,6 mA

Table 2: Stroke Output

Feedback Shaft Rotation

Min. 15°, max 90°
40° recommended for linear
applications

Table 3: Air Supply

Air Supply Quality

Free from moisture, oil and dust
per IEC 770 and ISA-7.0.01

Input Pressure Range

1,5 to 6,0 bar (22 to 87 psi)

Air Consumption (steady state)

0,08 Nm³/h @ 1,5 bar
(0,047 SCFM @ 22 psi)
0,12 Nm³/h @ 6,0 bar
(0,071 SCFM @ 87 psi)

Table 4: Output Signal

Output Pressure Range

0 to 100% of air supply pressure

Output Flow Capacity

2,4 Nm³/h @ 1,5 bar
(1,41 SCFM @ 22 psi)
7,0 Nm³/h @ 6,0 bar
(4,12 SCFM @ 87 psi)

Table 5: Shipping Weights

Base Positioner without
Accessories

1,2 kg (2,65 lbs)

Table 7: Environmental Conditions

Operating Temperature
Standard

-20 °C to +80 °C
(-4 °F to +178 °F)

Operating Temperature
Low

-40 °C to +80 °C
(-40 °F to +178 °F)

Transport and Storage
Temperature

-40 °C to +80 °C
(-40 °F to +178 °F)

Operating Humidity

0 to 100% non-condensing

Table 6: Performance Characteristics (typical)

Linearity

< +/- 1,0%

Resolution

< 0,3%

Repeatability

< 0,5%

Deadband

< 0,5%

Table 9: Limit Switches (optional)

Type

P&F SJ2-S1N

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-25 °C to 100 °C (-13 °F to 212 °F)

Type

P&F SJ2-SN

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-40 °C to 100 °C (-40 °F to 212 °F)

Type

P&F SJ2-N

Load current

< 1 mA < 3 mA

Voltage range

5 - 25 VDC

Hysteresis

0,2 %

Temperature

-25 °C to 100 °C (-13 °F to 212 °F)

3

LOGIX 510si OVERVIEW

The Logix 510si is a two-wire, 4-20 mA input digital valve
positioner. The Logix 510si positioner controls single-
acting actuators with linear and rotary mountings. The
Logix 510si is completely powered by the 4-20 mA input
signal. The minimum input signal required to function
is 3,6 mA.

Since the positioner is insensitive to supply pressure
changes and can handle supply pressures from 1,5 to
6 barg (22 to 87 psig), a supply regulator is usually not
required; however, in applications where the supply pres-
sure is higher than the maximum actuator pressure rating
a supply regulator is required to lower the pressure to
the actuator’s maximum rating (not to be confused with
operating range). A coalescing air filter is recommended

Table 8: Hazardous Area Specifications

ATEX

II1G Ex ia IIC T4 - T6
II3G Ex ic IIC T4 - T6

FM

Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C
Class I Zone = Group IIC T4 Ta = 85°C
Class I, Division 2, Groups A,B,C,D Temp. Class. T4 Ta = 85°C

CSA

Class I Division 1, Groups A,B,C,D
Class I Division 2, Groups A,B,C,D