9. Trouble shooting

Fault symptom

Change in input signal to positioner does
not affect actuator position.

Change in input signal to positioner ma-
kes actuator move to its end position.

Inaccurate positioning.

Action

• Check air supply pressure and connection
between positioner and actuator.

• Check input signal to positioner.

• Check output signal from I/P converter.

• Check mounting and connections of po-
sitioner and actuator.

• Check function of diaphragm block.

• Check input signal.

• Check mounting and connections of po-
sitioner and actuator.

• Uneven air supply pressure.

•Uneven input signal.

• Wrong size of actuator being used.

• High friction in actuator/valve package.

• Excess play in actuator/valve package.

• Excess play in mounting of positioner
on actuator.

• Defect or leaking diaphragm block.