9. Close the disc for centering the seatring, screw down

the retainer ring to keep the seatring in place.

10. Check that the seatring is centered. The play

shall be evenly applied between the disc and the

body.

Start to fasten the retainer ring by crosswisely

changing screws with evenly applied force.

11. The retainer ring shall more or less flush with the

valve body. If not, gently hammer with a plastic

hammer at the same time as the screws are

tightened.

12. Now you can mount the actuator and adjust the

end positions of the actuator until you get the

correct A-measure. This is described separately

below.

The valves seat ring should now be correctly prepared and

should not leak. Please note that PTFE can leak before it

becomes warm and adjusts to the disc. This is however a

small leakage and should not be considered. The valve

will be tight shortly.

9.4 To adjust a new seat ring in a valve with

manual operating lever or worm gear unit

1. Close the valve to the sealing position corresponding to

the value of dimension ”A” shown in Fig. 4.

2. Adjust the end stop of the operating lever or the worm

gear unit so that the sealing position will not be exceeded.

3. Tighten the retainer ring bolts in diagonally opposite pairs.

9.5

To adjust the seat ring in a valve with

pneumatic actuator

1. Turn the valve to closed position, although without

applying a sealing torque. The valve disc should then

only just be in contact with the seat ring in the valve

body.

2. Adjust the end position stop to the position in which the

valve is almost closed.

3. Connect the compressed air supply to the actuator. If

the end position stop is correctly set, the valve disc will

not move.

4. Adjust the end position stop until the actuator has

turned the valve disc to the sealing position, i.e.

dimension ”A” shown on the valve in accordance with

section 9.4 and Fig. 4.

5. Lock the end position stop so that the sealing position

will not be exceeded.

6. Tighten the retainer ring bolts.

9.6

To inspect and replace the upper stem seal:

9.6.1 Boxpacking of graphite type

The boxpacking usually requires inspection and adjustment

after the valve has been taken into service.

Ensure that the valve is not under pressure.

1.

Remove the actuator.

2.

Remove the nuts (29) and remove the gland

cover (23) and the boxpacking set (21).

3.

Clean the surfaces of the stem, gland cover (23)

and recess in the valve body.

4.

Carefully examine the stem surface which

must be completely free from marks and

scratches.

5.

Fit new boxpacking set (21). Then fit the gland

cover (23) and the nuts (29).

6.

Tighten the nuts (29) sufficiently to ensure that

the boxpacking is correctly seated and that it is

in contact with both the stem and the valve body.

Note: Check the condition of the boxpacking and, after the

valve has been taken into service, retighten the nuts (29), if

necessary.

Fig. 4. Adjusting a new seat ring.