Flowserve 505si Series Digital Positioner User Manual

Page 4

Advertising
background image

4

®

User Instructions Logix 505si - LGENIM0505-00 03/09

3

LOgix 505si OVERViEW

The Logix 505si is a two-wire, 4-20 mA input digital

valve positioner. The Logix 505si positioner controls

single-acting actuators with linear and rotary mount-

ings. The Logix 505si is completely powered by the 4-20

mA input signal. The minimum input signal required to

function is 3,6 mA.

Since the positioner is insensitive to supply pressure

changes and can handle supply pressures from 1,5 to

6 barg (22 to 87 psig), a supply regulator is usually not

required; however, in applications where the supply

pressure is higher than the maximum actuator pres-

sure rating a supply regulator is required to lower the

pressure to the actuator’s maximum rating (not to be

confused with operating range). A coalescing air filter

is recommended for all applications due to the close

tolerances in the positioner.

nOTE: The air supply must conform to ISA 7.0.01or

IEC 770 (a dew point at least 10 ˚C / 18 ˚F below ambi-

ent temperature, particle size below five microns – one

micron recommended – and oil content not to exceed

one part per million).

4 SPECiFiCATiOnS

Table 1: input Signal

Input Signal Range

4 - 20 mA

Compliance Voltage

6 VDC

Voltage Supply (maximum)

30 VDC

Minimum Required Operating

Current

3,6 mA

Table 2: Stroke Output

Feedback Shaft Rotation

Min. 15°, max 90°

40° recommended for linear

applications

Table 3: Air Supply

Air Supply Quality

Free from moisture, oil and dust

per IEC 770 and ISA-7.0.01

Input Pressure Range

1,5 to 6,0 bar (22 to 87 psi)

Air Consumption (steady state)

0,08 Nm³/h @ 1,5 bar

(0,047 SCFM @ 22 psi)

0,12 Nm³/h @ 6,0 bar

(0,071 SCFM @ 87 psi)

Table 4: Output Signal

Output Pressure Range

0 to 100% of air supply pressure

Output Flow Capacity

2,4 Nm³/h @ 1,5 bar

(1,41 SCFM @ 22 psi)

7,0 Nm³/h @ 6,0 bar

(4,12 SCFM @ 87 psi)

Table 5: Shipping Weights

Base Positioner without

Accessories

1,2 kg (2,65 lbs)

Table 7: Environmental Conditions

Operating Temperature

Standard

-20 °C to +80 °C

(-4 °F to +178 °F)

Operating Temperature

Low

-40 °C to +80 °C

(-40 °F to +178 °F)

Transport and Storage

Temperature

-40 °C to +80 °C

(-40 °F to +178 °F)

Operating Humidity

0 to 100% non-condensing

Table 6: Performance Characteristics (typical)

Linearity

< +/- 1,0%

Resolution

< 0,3%

Repeatability

< 0,5%

Deadband

< 0,5%

Table 8: Hazardous Area Specifications

ATEX

II 1G Ex ia II C T6

ATEX

II 3G Ex nL nA II C T4