Flowserve 505si Series Digital Positioner User Manual

Page 7

Advertising
background image

7

®

User Instructions Logix 505si - LGENIM0505-00 03/09

In order to determine if the loop will support the Logix

505si, perform the following calculation:

Available Voltage = Controller Voltage (@Current

MAX

)

- Current

MAX

*(R

barrier

+ R

wire

)

The calculated available voltage must be greater than

6.0 VDC in order to support the Logix 505si.

Example: DCS Controller Voltage = 19 V

R

barrier

= 300

R

wire

= 25

CURRENT

MAX

= 20 mA

Voltage = 19 V - 0,020 A*(300

Ω + 25 Ω)

= 12,5 V

The available voltage 12,5 V is greater than the required

6.0 V; therefore, this system will support the Logix

505si. The Logix 505si has an input resistance equivalent

to 300

Ω at a 20 mA input current.


The Logix 505si digital positioner has been designed to

operate correctly in electromagnetic (EM) fields found

in typical industrial environments. Care should be taken

to prevent the positioner from being used in environ-

ments with excessively high EM field strengths (greater

than 10 V/m). Portable EM devices such as hand-held

two-way radios should not be used within 30 cm of the

device.

Ensure proper wiring and shielding techniques of the

control lines, and route control lines away from elec-

tromagnetic sources that may cause unwanted noise.

An electromagnetic line filter can be used to further

eliminate noise (FLOWSERVE Part Number 10156843).

In the event of a severe electrostatic discharge near the

positioner, the device should be inspected to ensure

correct operability. It may be necessary to recalibrate

the Logix 505si positioner to restore operation.

8

STARTUP

8.1

Logix 505si Local interface Operation

The Logix 505si local user interface allows the user to

configure the operation of the positioner, tune the re-

sponse, and calibrate the positioner. The Local interface

consists of a quick calibration button for automatic zero

and span setting. There is also a switch block contain-

ing 4 switches. For indication of the operational status

or alarm conditions there are 3 LEDs on the local user

interface. This document describes the setting and use

of the Logix 505si user interface.

8.2

initial DiP Switch Setting

Before placing the unit in service, set the DIP switches

to the desired control options. For a detailed description

of each DIP switch setting, see sections below.

nOTE: The switch settings except the gain modifier

are activated only by pressing the Quick-Cal button.

The gain modifier switch is active at all times.

Operation of COnFigURATiOn DiP switch Setup

a.

Air Action - This must be set to match the configuration

of the valve/actuator mechanical tubing connection and

spring location since these determine the air action of

the system.

ATO (air-to-open)- Selecting ATO if increasing

output pressure from the positioner is tubed so

it will cause the valve to open.

ATC (air-to-close)- Selecting ATC if increasing

output pressure from the positioner is tubed so

it will cause the valve to close.

Figure 3: Compliance Voltage

510

Controller

Voltage

Compliance

Voltage

12V

505si

6V