6

®

User Instructions Logix 520MD - LGENIM0520-01 09/09

7 WiRing AnD gROUnDing gUiDELinES
Electrical connections:
signal cable with cable passage

(NPT or M20 x 1,5) to terminals 2 x 2,5 mm

input signal: 4 – 20 mA
nOTE: Observe the minimum requirements of voltage

and equivalent electrical load: 10,0 VDC / 500

/ at

20 mA

The performance is ensured only for a minimum input cur-

rent of 3,6 mA.

For wiring, the following notes should be observed:

nOTE: The input loop current signal to the Logix

520MD should be in shielded cable. Shields must

be tied to a ground at only one end of the cable to

provide a place for environmental electrical noise to

be removed from the cable. In general, shield wire

should be connected at the source. (Figure 2)

Connect the 4-20 mA current source to terminals +11 and

-12 (Figure 2).

grounding Screw
The grounding screw, located inside the positioner cover,

should be used to provide the unit with an adequate and

reliable earth ground reference. This ground should be tied

to the same ground as the electrical conduit. Additionally, the

electrical conduit should be earth grounded at both ends of

its run. The grounded screw must not be used to terminate

signal shield wires.

Compliance Voltage (Figure 3)
Output compliance voltage refers to the voltage limit the

current source can provide. A current loop system consists

of the current source, wiring resistance, barrier resistance

(if present), and the Logix 520MD impedance. The Logix

520MD requires that the current loop system allow for a 10 VDC

drop across the positioner at maximum loop current.

6 TUbing POSiTiOnER TO ACTUATOR
After mounting has been completed, tube the positioner

to the actuator using the appropriate compression fitting

connectors:

Air connections: 1/4” NPT (standard air connection)
Auxiliary power: Pressurized air or permissible

gases, free of moisture and dust in according with

IEC 770 or ISA 7.0.01.

Pressure range: 1,5 – 6,0 bar (22 – 87 psi)
For connecting the air piping, the following notes should

be observed:

1. The positioner passageways are equipped with filters,

which remove medium and coarse size dirt from the

pressurized air. If necessary, they are easily accessible

for cleaning.

2. Supply air should meet IEC 770 or ISA 7.0.01 require-

ments. A coalescing filter should be installed in front of

the supply air connection Z. Now connect the air supply

to the filter, which is connected to the Logix 500si series

positioner.

3. With a maximum supply pressure of 6 bar (87 psi) a

regulator is not required.

4. With an operating pressure of more than 6 bar (87 psi),

a reducing regulator is required. The flow capacity of

the regulator must be larger than the air consumption

of the positioner (7 Nm

3

/hr @ 6 bar / 4,12 scfm @ 87

psi).

5. Connect the outlet connector Y of the positioner to the

actuator with tubing, independent of the action (direct

or reverse).

Figure 2: Wiring Diagram

Table 10: Connection Table

Connection

Description

+11

Input+ 4..20 mA

-12

Input- 4..20 mA

+31*

Output+ 4..20 mA

-32*

Output– 4..20 mA

Limit switch 1 - separate board

Limit switch 2 - separate board

Y (0

⇒)

Pneumatic output signal (outlet)

Z (0

⇐)

Air supply

* 0ptional

Y

Z

Internal Housing

EARTH Terminal

4-20 mA Signal

Connect Shield at Source Ground

-

+

4-20 mA Current Source

Shielded Cable