Figure 3: compliance voltage, 510 controller voltage, 520md – Flowserve 520MD Digital Positioner User Manual

Page 7

Advertising
background image

7

®

User Instructions Logix 520MD - LGENIM0520-01 09/09

CAUTiOn: Never connect a voltage source directly across

the positioner terminals. This could cause permanent

circuit board damage.

In order to determine if the loop will support the Logix

520MD, perform the following calculation:

Available Voltage = Controller Voltage (@Current

MAX

)


- Current

MAX

*(R

barrier

+ R

wire

)

The calculated available voltage must be greater than 10

VDC in order to support the Logix 520MD.

Example:

DCS Controller Voltage = 19 V

R

barrier

= 300

R

wire

= 25

CURRENT

MAX

= 20 mA

Voltage = 19 V - 0,020 A*(300

Ω + 25 Ω)

= 12,5 V

The available voltage 12,5 V is greater than the required

10.0 V; therefore, this system will support the Logix 520MD.

The Logix 520MD has an input resistance equivalent to 500

at a 20 mA input current.

8 CAbLE REQUiREMEnTS
The Logix 520MD digital positioner utilizes the HART

communication protocol. This communication signal is

superimposed on the DC 4-20 mA current signal. The two

frequencies used by the HART protocol are 1200 Hz and

2200 Hz. To prevent distortion of the HART communication,

cable capacitance and cable length restrictions must be cal-

culated. The cable length must be limited if the capacitance

is too high. Selecting a cable with lower capacitance/mm

rating will allow longer cable runs. In addition to cable

capacitance, the network resistance also affects the

allowable cable length.

65

(R

barrier

+ R

wire

+ 390

Ω)

Example:

R

barrier

= 300

Ω (if present)

R

wire

= 50

C

cable

= =

Max. Cable Length =

Max. Cable Length = = 1111 m

To control cable resistance, No. 24 AWG cable can be

used for runs less than 1500 m. For cable runs longer

than this, No. 20 AWG cable should be used.

Electromagnetic Compatibility
The Logix 520MD digital positioner has been designed

to operate correctly in electromagnetic (EM) fields

found in typical industrial environments. Care should

be taken to prevent the positioner from being used in

environments with excessively high EM field strengths

(greater than 10 V/m). Portable EM devices such as

hand-held two-way radios should not be used within

30 cm of the device.

Figure 3: Compliance Voltage

510

Controller

Voltage

Compliance

Voltage

12V

C

network

(µF) < - 0,0032

72

ρF 0.000072 µF

m

m

- 0,0032 = 0,08 µF= C

network

(µF)(Max)

65

(300 + 50

+ 390)

C

network

(µF)

C

cable

0,08 µF

0.000072 µF/m

520MD

10V