1. Screw stud bolts

(120) into body (010).

2. Insert stem

(040) from inside of body in such a way that the flat side is paral-

lel to body longitudinal axis.

3. Insert chevron packing

(100).

4. Install gland insert

(065), gland follower (060), safety washers (150),

hexagon nuts

(110) and grounding strap (170) also on valves with actuator.

5. Install hand lever

(070) on to stem (040) and tighten it using lock washer

(130) and hexagon bolt (140).

6. Insert first ball seat ring

(030) into body (010).

7. Insert ball

(050) to valve stem by pushing the ball in a downward motion

through valve body.

8. Turn hand lever 90° of longitudinal axis of body.

9. Install ball seat ring with pressure compen-

sation grooves

(035) on to ball (050).

10. Install side piece

(020) on to body (010).

11. Install body bolts

(080) and hexagon nuts

(090) and tighten by crisscross

method to recommended torques.

12. Assemble stop

(210) with

hexagon bolt

(220).

Disassembly instruction see register 13,

page 7