4 installation, 1 quick-check, Mark 100 – Flowserve Valtek Mark 100 Control Valve User Manual

Page 4

Advertising
background image

Flow Control Division

Mark 100

4

Mark 100 Installation, Operation and Maintenance Instructions

FCD FCAIM0100-02

4 Installation

1. Before installing the valve, clean the line of dirt, welding chips,

scale or other foreign material.

2. Whenever possible, the valve should be installed in an upright

position. Vertical installation permits easier valve maintenance.

a

CAUTION: Do not insulate extension bonnets that are
provided for hot or cold services.

3. Be sure to provide proper overhead clearance for the actuator to

allow for disassembly of the plug from the valve body. Refer to
Table 1 for the necessary clearance needed for valve disassembly.

Table 1: Valve Disassembly Clearance

Valve Size

(inches)

Clearance

inches

mm

6

10

254

8

13

330

10

14

356

12

16

406

14

18

457

16

20

508

18

23

584

20

25

635

24

31

787

30

37

940

4. Double-check flow direction to be sure the valve is installed

correctly. Flow direction is indicated by the arrow attached to the
body.

5. If welding the valve into the line, use extreme care to avoid

excess heat buildup in the valve.

6. Connect the air supply and instrument signal lines. Throttling

control valves are equipped with a valve positioner. Refer to the
appropriate positioner bulletin for connections, maximum air
supplies, and maintenance instructions.

a

CAUTION: On valves equipped with air filters, the air
filter must point down to perform properly.

NOTE: In some rare cases, the air supply must be limited to
less than 150 psi (10.3 bar). This is indicated on a sticker found
near the upper air port on the actuator cylinder. An air regula-
tor should be installed to ensure the supply pressure does not
exceed the line pressure indicated on the sticker.

4.1 Quick-check

Prior to start-up, check the control valve by following these steps:

1. Stroke the valve and observe the plug position indicator on the

stem clamp compared to the stroke indicator plate. The plug
should change position in a smooth, linear fashion.

NOTE: Due to excessive friction, graphite packing can cause the
plug stem to move in a jerky fashion.

2. Check for full stroke by making appropriate instrument signal

change.

3. Check all air connections for leaks.

4. Check packing box bolting for the correct adjustment. Refer to

the packing installation manual for specific details on maintain-
ing the style of packing supplied.

a

CAUTION: Do not overtighten packing. This can cause
excessive packing wear and high stem friction that may
impede plug movement.

5. Make sure the valve fails in the correct direction in case of air

failure. This is done by turning off the air supply and observing
the failure direction.

6. After a temperature excursion has occurred, bonnet flange bolt-

ing should be retorqued to ensure bonnet gaskets do not leak.
See Table 2.

Table 2: Recommended Body Bolt Torque Values

Bolt Size

Bolt/Stud Material

Carbon Steel

Stainless Steel

(inches)

ft-lb

N m

ft-lb

N m

7

8

230

312

150

203

1

350

474

220

298

1

1

8

510

691

330

447

11/4

730

990

460

624

1

3

8

1000

1356

630

854

11/2

1320

1790

840

1139

1

5

8

1710

2318

1080

1464

1

3

4

2170

2942

1400

1898

1

7

8

2700

3660

1700

2305

2

3350

4542

2100

2847

2

1

4

4050

5491

2530

3430

2

1

2

4850

6575

3010

4081

Advertising