Flowserve APEX 5000 Analog Feedback Options User Manual

Page 2

Advertising
background image

B00063-0 (AUTO-71) 4/00

Page: 2 of 4

© 2000, Flowserve Corporation, Provo, UT

Automax Valve Automation Systems

Installation, Operation and Maintenance Instructions

Calibration:

Caution: When adjusting units already installed and located in potentially explosive environments, disconnect power
before opening cover.

Resistive Feedback:

1. Change positioner input signal to rotate actuator/valve to fail or start position.
2. Note desired resistance value at fail or start position.
3. Connect an ohmmeter to feedback module terminal strip (see Figure 2 for wiring diagram).

Figure 1 – Breather Piping

Figure 2 – Resistive Feedback Diagram