To link DO.PV_D to DO.BKCAL_OUT, configure
the IO_OPTS for the desired block to “PV for
BKCAL_OUT.” Note: This action prevents the use
of “Invert” as an IO Option.
Then, link BKCAL_OUT
to the BKCAL_IN of the function block sending the
CAS_IN_D signal.

Auxiliary Dry Contact Input

The BUSwitch

TB also monitors continuity across

terminals P4. This status is seen in the external alarm
parameter and in the OUT_D of DI-2. DI-2.OUT_D
will read Discrete 1 when no continuity exists and the
“Normally Closed” J1 and J2 jumpers are selected.
When contact is made in this jumper mode, the out-
put changes to Discrete 0.

To reverse the outputs, change the J1 and J2 settings
to “Normally Open.” Refer to Figures 3 and 4 for the
jumper settings.

Odometer Function

TB Parameter ODOMETER reports the number of
open-closed and closed-open transitions. It may be
reset using the RESET_ODOMETER parameter.
Simply write a “True” value to this parameter to reset.

Valve Stroke Time Out Function

The BUSwitch

times each valve stroke and

reports the time from the move command until the
appropriate position switch is tripped. The stroke
time is displayed in the transducer block parameter
“TRANSITION TIME.” If the “TRANSITION TIME” is
greater than the value entered in “TIME-OUT,” an
alarm is generated. This alarm is displayed in the
transducer block parameter “TRANSITION-ALARM”
and is also sent to the DI-1 block “OUT-D.” This is
a “linkable” input and can be used to alter process
control. The alarm will stay present until the “RESET-
TIMEOUT” parameter is set to “TRUE” in the trans-
ducer block.

Additional TB Parameters

Several TB parameters exist to store information
about the valve, actuator and BUSwitch

device.

In addition, calibration information may be stored.
Refer to the complete list of BUSwitch

TB

parameters starting on page 11 for a description
of these parameters.