Fieldbus Protocol

Installation, Operating and Maintenance Instructions

Flowserve Corporation

1350 N. Mountain Springs Parkway

1978 Foreman Dr.

Flow Control Division

Springville, Utah 84663-3004

Cookeville, TN 38501

www.flowserve.com

Phone: 801 489 8611

Phone: 931 432 4021

8. Using the DO-1.OUT_D value parameter (and

DO-2.OUT_D for dual coil mode), stroke the valve
(Discrete 0 = de-energized; Discrete 1 = energized)
and set limit switches, referring to “Adjustment of
Switch Cams” section. Circuit board mounted LED’s
light when switches are tripped.

9. This is the minimum configuration to operate

the actuator and read valve position. Refer to
F

OUNDATION

®

Fieldbus standards for DO and DI

blocks to establish more sophisticated control
strategies. Refer to the block sections in this manual
for more information on BUSwitch

functionality.

Mechanical Installation

BUSwitch

Mounting:

1. Installation is best performed with Flowserve

NAMUR mounting kits. These kits allow direct
mounting of the BUSwitch

shaft to the actuator

pinion without a coupler. The NAMUR mounting
kits will work with any actuator conforming to the
NAMUR standard for accessory mounting hole
locations and pinion dimensions. Simply attach the
bracket to actuator and BUSwitch

to the bracket

with the included fasteners. The BUSwitch

shaft

features an integral alignment pin that engages the
tapped pinion hole. Flowserve also offers a full line
of non-NAMUR mounting kits.

Spool and Tubing Configuration:

The following instructions apply to BUSwitch

config-

ured with integral pilot valves and spool valve. For
non-integral pilot/spool valves, follow manufacturer's
instructions for piping.

1. For spring return actuators, a 4-way spool valve is

provided with port #2 plugged. For double acting
actuators, the same valve is provided with no
plugs. Make sure the correct spool is selected
before installing tubing.

2. Make sure all air pressure is removed before

installing tubing.

3. Attach tubing according to Figures 1 or 2 at right,

depending upon application. Attach supply tubing
to Port 1 and use 3 and 5 for exhaust.

4. To prolong actuator life use only clean, dry plant

air. Lubricated air is not required, although it is rec-
ommended, particularly for high cycle applications.

4

2

3

1

5

5

3

1

2

4

Figure 1

Figure 2

Lubrication

All BUSwitch

spool valves are pre-lubricated

and will operate dry (with no additional lubrication).
The use of lubricated air will not interfere with the
functioning of the BUSwitch

. If air lubrication

is used, the oils listed below are popular, easily
obtainable, fluids that are recommended for use
with the BUSwitch

spool valve: Gulf Harmony 47,

Mobil DTE Medium, Shell Tellus 29, Texaco Rondo B,
Sohivis 47 and Sunnis 921. Many other lubricants are
acceptable providing they do not contain detergents
that will attack Buna N or Viton Seals.

AXAIM020-01

(AUTO-48)

3/03

Page 4 of 16

© 2003, Flowserve Corporation, Printed in U.S.A.