Flowserve ACE Series Centura User Manual

Page 7

Advertising
background image

©

2004, Flowserve Corporation, Printed in U.S.A.

3-Position Control/Dribble Control

SR Limit Switch Method

Accord Controls

Installation, Operation and Maintenance Instructions

Flowserve Corporation

1350 N. Mountain Springs Parkway

Phone: 801 489-2234

Flow Control Division

Springville, Utah 84663-3004

Facsimile: 801 489-2228

www.flowserve.com

FCD ACAIM0075-00 (AC-75) 08/04

Page 7 of 8

Typical Actuator Specifications

Action

Reversible

Range of Adjustability

0

°

-270

°

Supply Voltages

AC:

115 VAC

+/-10%

230 VAC

50/60 Hz

24 VAC

DC:

12 VDC
24 VDC

Temperature Rating

-40

°

F (-40

°

C) to 160

°

F (70

°

C)

Enclosure Ratings

Nema 4, 4X, 7, 9 Watertight and Explosion-proof
Class I Groups C&D, Div. 1&2
Class II Groups E, F&G, Div. 1&2

Motor Types

AC:

Permanent Split Capacitor, Class B Insulation

DC:

Brush

AC Motor Thermal Protection

Automatically resetting

Travel and Aux. Switches

SPDT, Form C
15 amp 125 VAC 1/2 HP,
10 amp 250 VAC, 1/2 amp 125 VDC

Conduit Connections

3/4-14 NPT

Manual Override

300 In-lbs max input

Corrosion Protection

Chromate conversion undercoat with
polyester electrostatic powder top coat

Terminal Strip Hookup

300V, 30 amp, 12-26 AWG

Lubrication

Permanently lubricated

Gear Train

Heat treated alloy steel able to
withstand stall torque

Note: The above ratings may change depending on model configurations and options provided.

Products may differ as the result of the Company policy of continuous product improvement.

Notes:
1. Duty cycle is the limit of “on” time as percentage of total cycle time. For example, the CE2 with standard

motor runs 3 seconds to open or close the valve. The motor must remain off for 9 seconds prior to
starting the close cycle. DC motors may be operated continuously.

2. Do not lock up DC motors.
3. CE5 duty cycles for AC motors are 20% for standard duty and 70% for extended duty.
4. For 180 degree applications, simply multiply the above cycle times by 2.

Run

Locked

Cycle Times in Seconds per 90 Degrees

Motor

Motor

Duty

Current

Rotor

Actuator Model

Option

Voltage

Cycle (1, 3)

(Amps)

(Amps)

CE2

CE4

CE7

CE1

CE5

Std.

115 AC

25

1.1

1.3

3

5

6

11

18

A

115 AC

Extended: 75

0.5

0.6

6

10

17

24

36

B

12 DC

100

1.6

3.0 (2)

6

9

16

21

32

C

24 DC

100

0.9

2.0 (2)

6

8

15

20

30

D

230 AC

25

0.7

0.8

3

5

6

11

18

F

230 AC

Extended: 75

0.3

0.4

6

10

17

24

36

J

24 AC

100

0.5

0.8

3

5

6

11

18

Actuator Model

CE2

CE4

CE7

CE1

CE5

Torque (In-Lbs)

250

400

700

1000

1500

Torque (N-M)

28

45

79

113

169

Weight (Lbs)

18

18

18

18

20

Weight (Kg)

8

8

8

8

9

Advertising