8

Operation

Activity

Indication

Function

Level electrode exposed

Green LED

for level electrode  is illuminated

Output contacts are closed.

Signal output  is open.

Alarm

Level electrode submerged,

high water level (HW)

exceeded.

Red LED

for level electrode  is flashing

De-energizing delay is running.

Signal output  is closed instantaneously.

Red LED

for level electrode  is illuminated

Delay time has elapsed, output contacts open.

Signal output  is closed.

Test channel 1

During operation:

Press and hold down key 

until the end of the test, level

switch must function as if there

were an alarm.

Red LED

for level electrode  is flashing

Alarm simulated in channel  or .

De-energizing delay is running.

Signal output  is closed instantaneously.

Red LED

for level electrode  is illuminated

Delay time has elapsed, output contacts open.

Signal output  is closed. Test finished.

Operation, Alarm and Test

Indicators and adjustors

Fig. 14

Level electrode 1

Test & diagnosis

button

LED alarm  /

operating mode

Diagnosis LED

Attention

Before carrying out the fault diagnosis please check:
Mains supply:

Is the level switch supplied with the mains voltage specified on the name plate?
Wiring:

Is the wiring in accordance with the wiring diagram and the relevant schematic

representation of arrangement?

Troubleshooting

Indication, diagnosis and remedy