Technical data – Flowserve NRS 1-51 User Manual

Page 8

Advertising
background image

8

NRS 1-51

Supply:
Mains voltage

4 VDC +/– 0 %, 0.3 A or 00 – 40 VAC +0/–5 %, 47 – 63 Hz, 0. A
External fuse

0.5 A (semi-delay)
Power consumption

7 VA
Inputs:
Electrical connection of level electrode

 input for level electrode NRG ...-5, NRG ...-, 4-poles with screen

Sensitivity 0.5 μS/cm or 0 μS/cm (at 5 °C).
Stand-by input

 volt-free input, 8-36 VDC, for monitoring the purging and bypass time.

Max. bypass time: 5 minutes.
Outputs:
Control circuit

 volt-free make contacts, 4 V DC – 50 V AC, max. 6 A (resistive/inductive),

Contact material AgNi.

Delay of response: 3 seconds.

Provide inductive loads with RC combinations according to manufacturer's specification to ensure

interference suppression.
Signal output

 volt-free output for instantaneous external signalling, 4 – 30 V AC/DC, max. 00 mA.
Indicators and adjustors

 buttons for test and diagnosis,

 red/green LEDs for indicating the operating mode and alarm.

3 red LEDs for diagnosis.
Housing

Housing material: base: polycarbonate, black; front: polycarbonate, grey.

Cross section of connection:  x 4.0 mm



solid per wire or

 x .5 mm



per stranded wire with sleeve to DIN 468 or

 x .4 mm



per stranded wire with sleeve to DIN 468; terminal strips can be detached

Fixing of housing: Mounting clip on supporting rail TH 35, EN 6075
Electrical safety

Degree of contamination: , overvoltage category III to EN 600-0.
Protection

Housing: IP 40 to EN 6059

Terminal strip: IP 0 to EN 6059
Weight

approx. 0.5 kg

Technical Data