Use the two code switches at the rear of the TRS 5-8 to adjust the temperature limits,
Fig. 5.

Adjust

MAX

/

MIN

Temperature Limits

Example 1

Requested temperature limit

τ

max

= 176 °C. The 8-pole code switch shows values

between “2” and “256”. The basic temperature is 30 °C. Set the “2”, “16” and “128”
switches to the left using a small screwdriver. The sum of the three values gives a
temperature of 146 °C, plus the basic temperature of 30 °C. This corresponds to the
requested temperature limit

τ

max

= 176 °C.

Example 2

Requested temperature limit

τ

max

= 446 °C. Set the “32”, “128” and “256” switches to

the left using a small screwdriver. The sum of the three values gives a temperature
of 416 °C, plus the basic temperature of 30 °C. This corresponds to the requested
limit temperature

τ

max

= 446 °C.

Example 3

Requested temperature limit

τ

min

= 79 °C. Set the “16” and “32” switches to the left

using a small screwdriver. The sum of the two values gives a temperature of 48 °C,
plus the basic temperature of 30 °C. This corresponds to a limit temperature

τ

min

=

78 °C. An adjustment of exactly 79 °C is not possible as temperatures can only be
adjusted in steps of 2 °C.

Tool

Screwdriver for slotted screws, size 2.5, completely insulated according to
VDE 0680.

Switch on mains voltage. The green LED will be illuminated. Fig. 5

Commissioning

Check whether the TRS 5-8 has been wired to its associated system components
TRG 5-... according to the wiring diagram. Fig. 1, Fig. 6 or Fig. 7.

Check wiring

Apply mains voltage

3