Wiring

Connecting line of temperature sensor for detecting the temperature of the installation

Use screened three-core cable (e. g. Ölflex 0 CH, manufactured by LAPP, 3 x 0.5 mm²) for connecting

the sensor. Max. cable length between temperature sensor and test station NRA -3: 50 m. Connect

screen to the sensor.

Connecting line of measuring electrodes

NRG 16-19

The measuring electrode comes with a  m long connecting line and can be directly plugged into

the test station NRA -3. An extension is possible with screened two-core cable, e. g. Ölflex 0 CH,

manufactured by LAPP,  x 0.5 mm². Max. cable length between temperature sensor and test station

NRA -3: 50 m. Connect screen to the distribution substation.
NRG 16-27, NRG 16-28

Use screened five-core cable (e. g. Ölflex 0 CH, manufactured by LAPP, 5 x 0.5 mm²) for connecting

the electrode. Max. cable length between measuring electrode and test station NRA -3: 50 m.

Connect screen to the connecting coupler.

Wiring

NRA 1-3a
With the base part taken off:
. Loosen the cable glands and pull the connecting lines through the glands.
. Remove approx. 3 cm of the end insulation of the cable and the screen.
3. Connect the wires to the terminal strips (rear of base part) according to the wiring diagram and use

a cable tie for securing the cable bundle to prevent misalignment.

4. Tighten cable glands to achieve a good seal. Use sealing plugs to seal off cable glands that are not

used.

NRA 1-3e
. Remove approx. 30 mm of the cable end insulation.
. Connect the wires to the terminal strips (rear of base part) according to the wiring diagram.

Attention

n

To protect the output relays provide the circuit with a T .5 A (slow blow) fuse.

n

To suppress interferences provide connected contactors with RC combinations as

specified by the manufacturer.

n

Install an easily accessible disconnector that serves as means of

isolation from the

electrical supply near the test station (EN 600-).

n

Label this disconnector as means of isolation for the test station.