Operation, Alarm and Test

– continued –

Mode , 6: After the mains voltage has been switched on and the display test has been finished the

system temperature, error messages and current alarms will be indicated.
Mode  to 5 and 7: After the mains voltage has been switched on and the display test has been finished

error messages and current alarms will be indicated.
For more information on the codes HIS, Int and tSt see section “Alarm list, Maintenance interval and

Test”, mode  to 7.

Start

SYS / °C

Key E

briefly

← longer

HIS

Keys

()

↓ (3) ↑

InT

Keys

()

↓ (3) ↑

dtS

Key E

briefly

← longer

ALL

Key E

briefly

← longer

Change

temperature

Keys (),(3)

Key E

briefly

don

dtS

Keys

()

↓ (3) ↑

C.xx

Key E

briefly

← longer

Change

temperature

Keys (),(3)

Key E

briefly

don

C.xx

Setting banking-up of condensate, mode 1 and 6

The precondition for this operating mode is:

n

the use of the measuring electrodes NRG 6-7, NRG 6-8 (with integrated condensate

temperature measurement at the steam trap)

n

the use of a separate temperature sensor for the measurement of the system/(plant) temperature

With the parameter

dtS the difference between the condensate temperature in the steam trap and the

plant temperature can be modified either globally for all steam traps (ALL) or for each individual trap

(C.xx). The factory set default value is 40 K. The value can be changed in increments of  K up to a max.

limit of 00 K.