Commissioning, Operation – Flowserve ER 50-1 User Manual

Page 16

Advertising
background image

6

. Check the switching function “High Level Alarm (HW)” of the electrode tip

4 .

For this purpose raise the water level in the vessel above the high water mark. As soon as the water

exceeds the high level mark the level switch must trigger a high level alarm.

. Check the switching functions “Pump ON” and “Pump OFF”,

see table “Functions”.

Commissioning

. Make sure that the system ER 50-/ ER 56- has been wired in accordance with the wiring diagram,

Fig. 11.

. Make sure that the mains supply corresponds to the wiring carried out on the equipment.

Checking electrical connection

Checking the assignment of the switching functions

Operation

ER 50-1, ER 56-1

Operation in conjunction with level switch NRS - for fill and discharge control with first low level

alarm.

Operation in conjunction with NRS -5 for fill and discharge control with high-level alarm.

Operation in conjunction with NRS - as first low-level alarm and high-level alarm in (pressurised) hot

water and steam plants to TRD 40, TRD 60, TRD 604, EN 95, EN 953 or according to national

regulations.

Operation in conjunction with NRS -3 as water level limiter with test button for steam boilers up to

max. 0.5 bar or in feedwater or condensate tanks.

Note

Should malfunctions occur during the commissioning procedure refer to chapter

“Troubleshooting” on page 7 in order to analyse and correct them.

Water level limiter