Flowserve FPS 14 User Manual

Page 9

Advertising
background image

4. Are the check valves installed in the proper direction?

Make sure the flow arrows on both of the check valves are in the same direction and match the

flow arrow on the pump tank. If the check valves are installed incorrectly, reinstall properly and
check for proper pump operation.

5. Are the check valves working properly?

There are two possible problems:

c.) The inlet check valve is stuck closed.

d.) The outlet check valve is stuck open.

iii.) If the inlet check valve is stuck closed, condensate will not be able to fill the tank.

To check the inlet check valve it must be removed from the line.

iv.) If the outlet check valve is stuck open, the condensate from the down stream side

will re-enter the pump tank. To verify this, close the outlet isolation valve. If the

pump begins to fill properly the outlet check valve could be stuck partially or
completely open.

If there appears to be a check valve problem, remove them from the pump. Check for any
debris or foreign matter blocking the check valve. Make sure that the check valve disc is not

canted or cocked. Push the disc with your finger, it should move freely and return to the closed
position. You will feel some resistance from the check valve spring when pushing the disc.

If the check valve(s) are good reinstall them and check for proper pump operation.

If the check valve(s) are damaged they must be replaced or repaired.

6. Is there water in the vent line?

A small amount of water is caused by the condensation of the venting motive gas and is not an

indication of a problem.

If a large amount of water is present in the vent line, there are two (2) possible problems:

a.) The mechanism has “hung up”.

b.) The float ball has collapsed.

Either problem would keep the mechanism from snapping at the top trip point, preventing the
pump from discharging condensate. If this is the case the mechanism will have to be removed

from the pump tank and inspected. See Maintenance Instructions.

7. Is the pump cycling?

Listen to the pump. During the proper operation of the pump, each complete cycle should be

noted by two (2) audible sounds. If a Gauge Glass is installed, check to see if the liquid level is
rising and falling. A Cycle Counter or Pressure Gauge will also indicate whether or not the

pump is cycling.

NOTE: If the condensate load is very low when the pump is being check, it would not be

unusual to have to wait for several minutes to verify proper pump operation.

If it is determined that the pump is not cycling, the mechanism must be removed from the tank
and inspected. See MAINTENANCE Instructions.

8. Check the operation of the vent and Pressure valves.

CAUTION: At the end of each pumping cycle, when the vent valve first opens, there will be a

puff of motive gas (Steam, air, or gas) as the tank is depressurizing. This is normal and should
not be mistaken for a leaking pressure valve. Be careful when troubleshooting, and only put

your hand near the vent after the initial puff disappears.

Advertising