Start-up, Operation, Alarms and Testing

– continued –

SRL 63-a

– continued –

The terminal strips of the logic unit SRL 63-a are electrically live during operation!
Because of the electrical currents which may flow, serious injuries are possible!
Before working on the terminal strips (assembly, disassembly, connecting the cables), al-
ways ensure that the unit is de-energized!
An external voltage is present at terminal strips X 1 (terminals 16 to 20) and X3 (ter-
minals 1 to 5).

Alarm

Standby period has expired
without purging process.

Red pilot lamp "Shutdown" is il-
luminated.

Safety circuit
interrupted.

Purging process not completed
in the specified purging time (5
min.).

For logic unit 1 and 2, the purg-
ing process is started simultane-
ously.

The safety circuit is only closed after completion of the purging process

(for sequence, see "Operation").

Testing the deactivation of the safety circuit

Press the button , then press
until the picture with the cursor
buttons is shown on the PLC dis-
play. Now press ESC and si-
multaneously (see picture
below).

The purging time is started.

When the purging time has end-
ed, the safety circuit is interrupt-
ed and then closed again after
5 seconds.

Press the button.

The display of Fig.6
is shown again.

Cursor picture in the PLC display

ESC + key