Factory setting

Basic Adjustments

– continued –

100 %

80 %
60 %

40 %

20 %

Fig. 7

Baud rate: 250 kb/s

Control equipment: 1

Node ID: 039

Control equipment: 2

Node ID: 040

Switchpoint 1: 80 %

Switchpoint 2: 60 %

Switchpoint 3: 40 %

Switchpoint 4: 20 %

The level switch features the following factory set default values:

Relay with energizing delay switchpoint 1: 1s

Relay with energizing delay switchpoint 2: 1s

Relay with energizing delay switchpoint 3: 1s

Relay with energizing delay switchpoint 4: 1s

Relay with de-energizing delay switchpoint 1: 3s

Relay with de-energizing delay switchpoint 2: 1s

Relay with de-energizing delay switchpoint 3: 1s

Relay with de-energizing delay switchpoint 4: 3s