Basic adjustments – Flowserve NRS 2-40 User Manual
Page 13
Advertising
13
Factory setting
Basic Adjustments
– continued –
100 %
80 %
60 %
40 %
20 %
Fig. 7
■
Baud rate: 250 kb/s
■
Control equipment: 1
■
Node ID: 039
■
Control equipment: 2
■
Node ID: 040
■
Switchpoint 1: 80 %
■
Switchpoint 2: 60 %
■
Switchpoint 3: 40 %
■
Switchpoint 4: 20 %
The level switch features the following factory set default values:
■
Relay with energizing delay switchpoint 1: 1s
■
Relay with energizing delay switchpoint 2: 1s
■
Relay with energizing delay switchpoint 3: 1s
■
Relay with energizing delay switchpoint 4: 1s
■
Relay with de-energizing delay switchpoint 1: 3s
■
Relay with de-energizing delay switchpoint 2: 1s
■
Relay with de-energizing delay switchpoint 3: 1s
■
Relay with de-energizing delay switchpoint 4: 3s