Commissioning, Operation, Malfunctions – Flowserve NRG 16-42 User Manual

Page 21

Advertising
background image

2

Turn on the power for level switch NRS -42.

Commissioning

Check whether the level electrode NRG 6-42 and the associated level switch NRS -42 have been

wired according to the wiring diagram.

Fig. 11

Check wiring

Apply mains voltage

Operation

During operation the level switch detects the level electrode via CAN bus.
The communication via CAN bus is faultless – there are no fault messages.

Level electrode with CAN bus

Note

To analyse and eliminate malfunctions refer to “Fault finding list for troubleshooting” on

pages 2 - 22.

Malfunctions

Fault finding list for troubleshooting

Fault:

In spite of correct wiring and commissioning of the equipment an interference signal

is indicated.

Remedy: The interference signal is caused by H. F. interferences coming from the installation. For

interference suppression of the voltage supply we supply ferrite rings, stock code 47253.

The 230 V supply lines should be looped through the ferrite ring five to ten times.

If several controllers are used in the system, they can be fed from the interference

suppressed supply lines. For the interference suppression of the bus line we supply

hinged-shell ferrite rings, stock code 47254. The hinged-shell ferrite rings are clamped

onto the bus line close to the terminal strip of the controller.

Equipment fails to work – Indication of a malfunction