Malfunctions – Flowserve NRG 16-42 User Manual

Page 22

Advertising
background image

22

Malfunctions

continued

Fault finding list for troubleshooting

continued

Fault:

The thermal fuse has been triggered.

Remedy: The ambient temperature must not exceed 70°C.

Fault:

The LED

I does not light up. No data exchange.

Remedy: Check level switch NRS -42. Connect electode according to the wiring diagram.

The equipment fails to work – no function

Fault:

LED “Power” does not light up.

Remedy: Apply mains voltage. Wire equipment according to the wiring diagram.

Switchpoints reached / level below switchpoints – no function

Fault:

The electrode housing does not have earth connection to the boiler.

Remedy: Clean seating surfaces and insert metal joint ring (of stainless steel .430) 33 x 39 to

DIN 7603. Do

not insulate compact system with hemp or PTFE tape!

Fault:

The electric conductivity is too low.

Remedy: Set sensitivity of level switch NRS -42 to ≥ 0.5 µS/cm.

Fault:

The isolating valves of the external measuring pot (optional) are closed.

Remedy: Open isolating valves.

Fault:

The vent hole in the protection tube does not exist, is obstructed or flooded.

Remedy: Check protection tube and, if necessary, provide vent hole.

Fault:

The electrode rods have earth contact.

Remedy: Change installation position.

Fault:

The switching function has not been correctly allocated. Electrode rods have been cut
to the wrong size.

Remedy: Identify electrode supply wire and reconnect the circuit board in the terminal box

accordingly.

Switchpoints reached / level below switchpoints – incorrect function

If faults occur that are not listed above or cannot be corrected, please contact our service centre or

authorized agency in your country.

Fault:

The internal seal of the electrode rod is damaged.

Remedy: Replace level electrode.