4

SDI/Wayne CAT Interface

SC II and CFN3

Gasboy CFN Series

See the SC3 Manager’s Manual for OS/2, chapter 16 for more information. The text editor on NT
is either NotePad or WordPad. See the CFN3 Manager’s manual, chapter 16 for more
information.

Make sure there is only one .B0’n’ and one .A0’n’ for each SDI box.

If you want to force the site to reload the application, DOWNLOAD SDI n where ‘n’ is the SDI
number. This will force a download.

SDI status will show up in the gate section of diagnostics. Use the command:

Print Diagnostics 1 (P Di 1)

to display the SDI status.

Checking the revision level of the Vista Card terminal

For the SDI interface to work with the Wayne CAT, the revision level of the Vista Card terminal
must be greater than 50. To check the revision level:

1.

Switch OFF the power to the Vista Card terminal.

2.

While holding down any key on the keypad, switch ON the power to the Vista Card

terminal. Hold the key down until the display reads “REV”, then release the key.

3.

The unit will then enter the self test mode. It will wait 25 seconds for the response

to self test prompts, then proceed to the next test (after the last test) revert to on-line
mode.

The first display in the self test shows:

REV XXX XX/XX/XX
ADDRESS = XX

The top row is the Vista Card terminal software revision level and the bottom row is the

currently assigned terminal address for the card processing terminal communication data link.
The top line must display the revision level of 50 or greater.

Press

to

exit.

Follow the instructions in the manual Installation Operation, Vista Series from Wayne

Dresser for completing the self test.

Site Controller Software Configuration

Version 2.2 or later of the Site Controller software is required to run a Wayne CAT. The CAT
should be on the RS-422 port.

All readers that are to be CATs must be set up in the Reader configuration to be device type

Wayne CAT. The Reader Parameter “TYPE” (device type) must be changed to 8, for Wayne
CAT.

Reader Addresses

No reader can be set to the address of 30, that is reserved for the Master Security Module. The
reader that would have been 30, give the address of 40. The Site Controller will read the address
as 30.