Installation, Program switches, Wiring schematics – Greenheck Advanced Control - MSAC (476373) User Manual

Page 2: Warning, Mounting, Wiring, Low voltage wiring, Torque table, Switch 1, Switch 2

Advertising
background image

2

Motor Starter Advanced Control

WARNING

• To maintain overcurrent and short circuit protection,

the manufacturer’s instructions for selecting current
elements and setting the instantaneous-trip circuit
breaker must be followed.

• Tripping of the instantaneous-trip circuit breaker

is an indication that a fault current has been
interrupted. Current-carrying components of the
magnetic motor controller should be examined and
replaced if damaged to reduce the risk of fire or
electric shock.

• Do not locate starter in an environment subject to

flammable gases, dusts or materials. Contact arcing
can induce explosion or fire.

• Locate starter in a location appropriate to enclosure

ratings and operational ratings. (e.g. NEMA-1 should
only be located in a dry, protected environment).

• Do not allow any metal shavings or debris from

installation to enter enclosure.

Installation

Mounting

Mount the starter on a vertical surface, with the line
terminals facing up. Install using 1/4-inch diameter
hardware suitable for the mounting surface.

Wiring

Wire main power input and motor leads to the
appropriate terminals tightened to specified torques
indicated in the torque table. Use only copper
conductors rated at least 60°C for applications less
than 100A and at least 75°C ≥ 100A. Maintain proper
clearances and verify that no possibility of an electrical
short exists between the power conductors or
enclosure. Ensure that wires are not under stress and
all insulation is intact. Verify voltage input matches label
and the control power is tapped per schematic.

Low Voltage Wiring

Automation system control wiring should be run in
a separate conduit. The control terminals accept
26~14AWG wire torqued to 3.5 in-lb.

Program Switches

SWITCH

1

Smartstart Bypass: Bypasses the Smartstart features
when on. Smartstart protects the motor by detecting
several common potentially damaging fault conditions.
When Smartstart is active, the starter will shut off
under the following conditions: if locked rotor condition
is present for 0.5 seconds, if the motor takes more
than 10 seconds to start, or if the FLA setting is
determined to be incorrect.

SWITCH

2

Selects overload trip Class 10 when on and overload
trip Class 20 when off. If trip Class 20 is selected
Smartstart is bypassed. Default: ON

SWITCH

3

(ON) - Fault reset: Depress the “OFF” button for 5
seconds to reset a fault trip. Starter will return to “OFF”
mode.
(OFF) - Automatic Fault Reset: The starter will make 3
attempts at an auto fault reset separated by 5 minutes
intervals. Also allows manual reset as above.

SWITCH

Power Fail Modes

4

5

ON

ON

Default Mode - Always return to last mode with no
delay in the event of a power failure.

OFF OFF

Default Mode - Always return to last mode with no
delay in the event of a power failure.

ON

OFF

Always return to last mode with a 10 second delay in
the event of a power failure.

OFF

ON

Upon a power failure, return to off mode.

NEMA

Size

Input (lb-in)

Output (lb-in)

Standard

Combination Motor Leads

00

15.6

18

20

0

15.6

18

20

1

15.6

18

20

Torque Table

Wiring Schematics

Standard product wiring diagram shown. As-built
product wiring may vary. Product wiring diagram located
on starter enclosure.

H1

H4

L3

L1

L2

MTR

T1

T3

AUX

CONT

M

T2

OL

3PH

43

44

31

32

A1

A2

M

Control

Limit Switch

Normally
Open Input

Actuator

Control

24VDC,
1A Output

Dry

Inputs

Relay

Outputs

Common

Fault

Status

Fireman’s

Override

12-250VAC/DC Input

Auto Run

Permissive

Shut Down

Auto Run

12-250VAC/DC Input

Voltage

Inputs

Contactor

Coil

1

FLA (A)

5

10

15

20

25

30

35

40

PCB Power

H1 H4

Keypad

Overload Setting

Normally
Open Input

Normally
Open Input

Normally
Closed Input

MCP

(Optional)

24V
Output to
contactor coil

208-600VAC
60VA Max.

208-600VAC
Input

24VDC output

to 24VAC

contactor coil

®

Advertising
This manual is related to the following products: