Motor Starter Advanced Control

Protective Features

Electronic Overload Operation

When an alarm occurs, the type of alarm will be
indicated by flashing a combination of the hand/off/auto
LED’s as indicated in the table.

Cycle
Fault

Trips when the starter is activated at a rate
exceeding 20 starts per minute.

Short 24V

Trips if the starter’s combined current drawn
from the 24VDC damper actuator terminals
and contactor terminals exceeds 1 amp.

Locked
Rotor

Trips when a locked rotor condition is
detected for 0.5 seconds (Smartstart mode
only).

Max Start
Time

Trips if the motor takes more than 10 seconds
to start (Smartstart mode only).

Out of
Calibration

Trips if the FLA setting is determined to be
incorrect based on the motor inrush current
(safety start mode only).

Stall

Trips if a STALL condition is detected. (0.5
seconds at 300% FLA and current slope not
decreasing). Disabled during startup.

Overload

Overload trip Class 10 or 20. Trip current =
115% of FLA. Trips when the load is greater
than the Full Load Ampere setting labeled
FLA- (1-40A). The trip time will be determined
by the Class 10/20 DIP switch.

Phase
Unbalance

Trips in the event of a phase failure or phase
unbalance greater than 70% (Smartstart
mode only)

Fault

Hand

Off

Auto

Cycle Fault Alarm

Short 24V Alarm

0

Locked Rotor Alarm

0

Max Start Time Alarm

0

0

Out of Calibration Alarm

0

Stall Alarm

0

0

Overload Alarm

0

0

Phase Unbalance Alarm

0

0

0

– = off 0 = on

* Run and Fault LED’s will blink together in the event of a

hardware fault.

Operation

• Intended for use with 3-Phase, 50/60Hz

• Accepts 208-600VAC, ±10%

• Short Circuit (RMS, Symmetrical)

Stand-Alone Overload Unit - 200 KAIC, 600V Max.

Standard Starter - 5 KAIC, 600V Max

Combination Starter - 100 KAIC, 240V Max.

30 KAIC, 480V Max.

10 KAIC, 600V Max.

• Ambient Operating Temperature = -20°C to 60°C

• Ambient Storage Temperature = -40°C to 85°C

DANGER

• Ensure that all connections are properly

torqued and enclosure is closed prior to
applying power to the device.

• Ensure all mechanical equipment operated by the

starter is clear for safe operation in case of starter
activation.

• When in AUTO mode, starter may be activated

remotely by the control system.

!

!

Operation Modes

ON (HAND): Press the ON mode button to manually
engage motor.

OFF (RESET): Pressing the OFF mode button
manually disengages the motor. Additionally, the OFF
button serves as a manual Reset. Press and hold
OFF for 5 seconds to Reset the starter after a fault
trip.

AUTO: When utilizing AUTO mode, the starter is
controlled by a remote Start/Stop command.

LED Status Indicators

MODE LEDs: Illuminates with corresponding mode
selection (HAND/OFF/AUTO). Flashing mode LED
signals a fault trip during the last operating mode.
All three mode LEDs will flash simultaneously during
Shutdown or Fireman’s Override operation.

RUN LED: Illuminates when starter is given a Run
signal and proof of flow is detected. LED will flash
when Run signal is present without proof of flow to
motor.

FAULT LED: Illuminates upon a fault condition or
overload trip. Starter must be returned to the OFF
mode in order to Reset.

Keypad Interface

1

FLA (A)

5

10

15

20

25

30

35

40

C-

C+

V3

V4

V1

V2

D5

D6

D3

D4

L-

L+

A-

A+

D1

D2

O1

O

O

2

CONTACTOR

COIL

LIMIT

SWITCH

D

AMPER/

AC

T

U

A

T

O

R

DR

Y

AU

T

O

DR

Y

PERMISS

DR

Y

SHUTDO

W

N

RELA

Y

S

F

A

UL

T ST

A

TUS

12-250V

FIREMAN’S

12-250V

AU

T

O

1

2

3

4
5

OFF ON

NOTE

On NEMA-4X

Enclosures, the

interface is inside

the enclosure.

Do not attempt

to remove the

keypad on exterior

of enclosure.

®