I. GENERAL INFORMATION

Warranty

1. Herrmidifier warrants to the buyer or any user during the

duration of the Warranty that the humidifier described

in this manual will be free from defects of material and

workmanship for a period of three (3) years from the

date of shipment.

2. For this Warranty to be effective, this humidifier must

be installed, operated and maintained in accordance

with the Installation Instructions, Operations and

Maintenance Manual(s) supplied with the humidifier.

3. In the event of a defect or malfunction in this product during

the Warranty Period, user may contact the Customer

Service Department or their Herrmidifier Representative

for a Material Return Authorization (MRA) number. Items

tagged (on the outside of the box) with this number may

be returned to Herrmidifier for replacement. Incidental

expenses such as cost of transporting the humidifier

to Herrmidifier or labor associated with removal/

replacement of the parts shall be paid by the user. Upon

completion of the reconditioning, the humidifier will be

returned at no cost to the user. Items returned without

an MRA number will not be accepted!

4. This Warranty does not cover field labor for

repairs to this humidifier or any special, indirect or

consequential damages. Some states do not allow

the exclusion or limitation of incidental or consequential

damages, so the above limitation may not apply to you.

5. If, after a reasonable number of attempts to do so,

Herrmidifier is unable to remedy any defects or

malfunctions in this humidifier, then the user may elect

either a replacement of such product or part which may

be defective without charge or a refund of the buyer’s

original purchase price.

6. This Warranty gives you specific legal rights, and you

may also have other rights which vary from state to

state.

NOTE

Water quality plays a vital role in the performance and

maintenance requirement of any humidifier. Adjust-

ments to the circuit board may be necessary based on

the incoming water quality.

Performance problems associated with water quality

are not warranty issues!

Evaporative distance can be measured in two ways.

“Bulk” evaporative distance beyond which condensation

will not occur on objects at duct temperature. “Last

Wisp” evaporation is the point beyond which there is no

visible steam and it is safe to install high-efficiency filters.

Herrmidifier has published evaporative distance tables

for standard conditions (55°F, 70% downstream relative

humidity). Steam intensity and air velocity are evaluated at

these conditions. A second table is published which allows

correction to non-standard )other than 55°F and 70%

relative humidity downstream of the humidifier) conditions.

The tables are only useful with Herricane CS Series

humidifiers. Application to other brands of humidifiers is

not recommended. Differences in distribution patterns will

cause problems!

If you desire, you may forward your design criteria to Herr-

midifier for a written analysis of your evaporative distances.

We will be able to define the “bulk” and “last wisp” evapo-

rative distance based on this criteria only. If any changes

are made to the design, a follow-up analysis must be made

to assure fail-safe operation.