7.14.2 Heartbeat
Heartbeat is a failure monitoring mechanism which needs no RTR telegrams�

The sensor cyclically transmits a heartbeat message which contains the device

status� The master can monitor these telegrams� Heartbeat is activated as soon

as a value greater than "0" is entered in the register heartbeat interval time

(1017h)�

Heartbeat has a considerable influence on the bus load of the CANopen network - but generates a

bus load which is only half as high as node guarding / life guarding�

7.15 COB IDs
The CAN identifiers of the communication objects are determined according

to the pre-defined connection set with every reset (communication, application

and hardware reset) depending on the set node ID (2000h)�

Communication object

Calculation of the COB ID

Default value (node ID = 10)

NMT0 h

0h

SYNC

80h

80h

EMCY

80h + node ID

8Ah

TPDO1

180h + node ID

18Ah

Default SDO
(Client

server)

580h + node ID

58Ah

Heartbeat

700h + node ID

70Ah

7.16 Status LED (to CiA DR-303-3)
The integrated LEDs indicate the current device status (Run LED, green) and CAN

communication errors (error LED, red)�

LED

Description

Green
Off

The device is in the state "reset" or no power supply is available

Flashing

The device is in the state "pre-operational"

Brief lighting once

The device is in the state "stopped"

On

The device is in the state "operational"

Red
Off

No error

Brief lighting once

Error counter

The CAN controller has reached or exceeded its warning limit

Brief lighting twice

The device has detected the failure of the guarding master

(node guard event)

On

The device is in the state "bus off"