DESIGN & PERFORMANCE

Thermalboard 250' Loops 20¡F Temp Drop*

BTU/SQ/FT

10.00

15.00

20.00

25.00

30.00

35.00

40.00

Friction Loss (Ft. Head)

2.22

4.70

8.01

12.10

16.96

22.80

28.87

Water Speed (Ft./Second)

0.60

0.90

1.20

1.50

1.80

2.10

2.40

GPM Per Loop

0.18

0.27

0.36

0.45

0.54

0.63

0.72

Thermalboard 200' Loops 20¡F Temp Drop

BTU/SQ/FT

10.00

15.00

20.00

25.00

30.00

35.00

40.00

Friction Loss (Ft. Head)

0.98

2.07

3.53

5.33

7.47

9.93

12.72

Water Speed (Ft./Second)

0.45

0.68

0.90

1.13

1.35

1.58

1.80

GPM Per Loop

0.14

0.20

0.27

0.34

0.41

0.47

0.54

*Shaded areas have high head loss

DESIGNER’S NOTE

Remember average water temperature means the average of the supply and
return water temperatures flowing to and from the loop. Most typically
Infloorboard™ is designed with a 20F° temperature drop. This means the sup-
ply water temperature would typically be 10F° higher than the average water
temperature.

INFLOORBOARD™ 250’ LOOPS 20°F TEMP DROP•

INFLOORBOARD™ 200 LOOPS 20°F TEMP DROP