Legrand RC3 Receptacle Replacement User Manual

Page 2

Advertising
background image

2

WHITE or NEUTRAL
from branch circuit

WHITE

from poke-thru receptacle

BLACK or HOT
from branch circuit

BLACK
from poke-thru receptacle

GREEN (jumper wire)

from poke- thru junction box

GREEN

from poke-thru receptacle

CONVENTIONAL WIRING SCHEMATIC

WHITE or NEUTRAL
from branch circuit

WHITE
from poke-thru receptacle

BLACK or HOT

from branch circuit

BLACK
from poke-thru receptacle

GREEN (jumper wire)
from poke-thru junction box

ISOLATED GROUND
from branch circuit

GREEN
from poke-thru receptacle

ISOLATED GROUND WIRING SCHEMATIC

GREEN or GROUND
from branch circuit
SYSTEM GROUND

GREEN or GROUND
from branch circuit
SYSTEM GROUND

WARNING:

Ground wire from junction box must be connected to SYSTEM GROUND.

Step 5 Snap new receptacle into trim flange.

Step 6 Replace gasket and slide holder with the two #6-32

screws provided.

CAUTION:

Make sure bosses on receptacle match
up with cutout in the trim flange.

CAUTION:

Gasket must be set in place to provide
a scrub water seal.

CAUTION:

Receptacle mounting means not
grounded. Grounding wire connection
required. For isolated ground wiring,
connect ground leads to a separate
isolated grounding conductor.
See NEC250-146(d).

NOTE: Factory supplied junction box shown. Junction boxes

must be located in an accessible location. Poke-Thru
devices with an “LJB” or “LJB25” suffix are supplied
without a junction box (supplied by others).

CAUTION:

Do not over tighten cover mounting screws.

Step 7 Wire up connections in the junction box. Connect

poke-thru conductors according to required device
configuration. See schematic below.

Cat. No. RC37REC
or RC37REC-25