Legrand 2400 Series Steel Plugmold Multioutlet System v.2 User Manual

24r plugmold

Advertising
background image

Wiremold / Legrand electrical systems conform to and should be
properly grounded in compliance with requirements of the current
National Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand electrical
products may bear the mark as UL Listed and/or Classified and should
be installed in conformance with current local and/or the National
Electrical Code.

24R Plugmold

®

I N S T A L L A T I O N I N S T R U C T I O N S

Installation Instruction No.: 1 007 574 – February 2008

IMPORTANT: Please read all instructions

before beginning.

BACKFEEDING 24R PLUGMOLD

Step 1 Remove appropriate 1/2" trade size knockout

from the base.

Step 2 Feed cable through connector and

attach the base to the 2451 or 1/2"
trade size feed connector.

Step 3 Mount the 24R Plugmold base to the wall

using No. 8 flat head screws every 32" max.

Step 4 Cap wires at the end of the harness

on both sides using wire nuts.

Step 5 Cut and strip wires in appropriate location.

Connect feed wires to the harness using
wire nuts or W30 Connectors. (Wire Nuts and
W30 Connectors are sold separately.)

Step 6 Snap 24R Plugmold cover onto the base.

Advertising