Legrand PSHB120277L3 User Manual

Pass & seymour, Description and operation, Coverage

Advertising
background image

No: 341018 – 9/12 Rev. B

U.S. Patents: 5640113, 5804991

Pass & Seymour

®

High Bay • Line Voltage • Passive Infrared • Occupancy Sensor for Dry Locations
Grande hauteur • Tension secteur • Infrarouge passif • Détecteur de présence pour environnement sec
Montaje alto • Voltaje de línea • Infrarrojo pasivo • Sensor de ocupación para lugares secos

Installation Instructions • Instrucciones de Instalación • Notice d’Installation

Catalog Number(s) • Numéro(s) de Catalogue • Les Numéros de Catalogue: PSHB120277Lx

Country of Origin: Made in Taiwan • Pays d’origine: Fabriqué à Taïwan • País de origen: Hecho en Taiwán

PSHBEM

Extender

Module

Back

Box

PSHB120277

Sensor

Module

PSHBLx

Lens

or

Alignment Guides

O

PEN

C

LO

SE

Light Level

Adjustment

Trimpot

Surface

Mounting

Screw Hole

Surface

Mounting

Screw Hole

DIP Switches

PIR Sensor

(do not touch)

Detection

Indicator LED

DESCRIPTION AND OPERATION

The PSHB120277Lx occupancy sensors are designed for automatic lighting control in warehouse high bay dry

location applications. All models contain a passive infrared sensor (PIR). The PSHB120277Lx series sensors are

modular and are made up of a Power Module and a Lens. The coverage area is determined by the lens module.

There are three different lenses available. See the Coverage section for more information.
All models in the PSHB120277Lx series use a set of DIP switches to set the time delay and PIR sensitivity, as

explained below.

COvERAgE

Coverage patterns, density and range, are determined by the type of Lens attached to the PSHB120277Lx.

PSHB120277L1

The L1 Lens offers linear patterns best suited for high bay aisleway applications. The Fresnel lens is designed to

detect walking motion when mounted at or around 40’. In optimal conditions, the lens has a 60’ linear detection

range.

PSHB120277L2

The L2 Lens offers 360° coverage and is best suited for open area and aisleway coverage in high bay applications.

The L2 is a multi-cell, multi-tier Fresnel lens offering a high density coverage pattern that spreads over a 40’

diameter area at a height of 20’.

PSHB120277L3

Similar to the L2 Lens, the L3 offers 360° coverage, and is best suited for open areas and aisleways in high bay

applications. The L3 is a multi-cell, multi-tier Fresnel lens offering a high density coverage pattern.The L3

is designed for mounting at heights between 30’ to 40’, with a coverage area up to 60’ in diameter when mounted

at 40’.

INSTALLATION

CAUTION

Turn the power off at the circuit breaker before installing the sensor.

1. Determine the mounting location appropriate to the features of the power module and the coverage area. Careful

consideration must be given to sensor placement. Avoid placing the sensor where the edge of the fixture,

shelving or other obstructions may block the sensor’s line of sight. Mount the sensor below the edge of the fixture

and away from the fluorescent lamps so that the heat from the lamps does not affect the sensor.

2. Make sure that you have the appropriate accessories for the sensor mounting configuration. (See Mounting

Options.)

3. Assemble any necessary mounting accessories and attach them to the power module, making sure that the

flying leads from the power module are accessible.

4. Connect the line voltage and load wires to the sensor leads as shown in the Wiring Diagram for the unit’s

application.

• Do not allow bare wire to show.
• Make sure all connections are secure.
5. Restore power from the circuit breaker.

WIRINg

MOUNTINg OPTIONS

The PSHB120277Lx can be attached to the fixture or junction box using the back box and chase nipple or directly

to the fixture surface via the two screw holes provided in the Power Module (see Surface mounting below). The

Extender Module (PSHBEM) allows attaching the sensor to the side of the fixture in a number of configurations

using provided chase nipples.
Back box mounting requires a standard 1/2” knockout for the chase nipple. The Power Module mounts to the back

box with a bayonet type fitting requiring a slight twist of the units to separate them or lock them into place. The box

comes ready for side mounting. It can be modified for rear mounting as follows:
1. Pop out the cap in the rear knockout.
2. Un-snap the chase nipple from the side mount and snap into the rear mounting hole.
3. Use the cap to close the side mount hole.

4. The chase nipple provided can be pushed into a standard 1/2” knockout in a metal fixture [max of 1 mm (0.04”)

thick metal] without the need for the included internal nut. The nut can be used for added security if necessary.

The

PSHBEM extender module allows threading the wires through its chase nipples and into the fixture for

connection. The two sides of the PSHBEM are then snapped together to protect the wires. The short chase nipple

is designed to snap into the PSHBEM connection box while the longer chase nipple snaps into any metal fixture or

connection box with a standard knockout. The caps on the PSHBEM can be removed in various configurations to

allow moving the chase nipples and adjusting the height of the sensor on the fixture.

Using the back box and PSHBEM Extender Module

Surface mounting requires holes in the fixture to pass wires

and attach two #6-32 screws through the surface mounting

screw holes on the component side of the Power Module as shown.

ADjUSTMENTS

Sensor factory pre-sets are as follows (default settings are

bold):

Factory Switch Settings

1 2 3 4 5 6 7 8 9 10

ON OFF OFF OFF OFF ON ON OFF OFF OFF

PIR Sensitivity (switches 1 & 2) .......................

Medium 85%

Time Delay (switches 3-7) ...............................

15 Minutes

Overrides (switches 8-10) ............................... See table below for each model.

N/A = not applicable, no effect.
PIR Sensitivity (Switches 1-2)

The factory setting of 85% is suitable for most applications, but it may be necessary to adjust the PIR sensitivity

if there is any environmental interference causing false triggers or if sensitivity needs to be increased for your

particular application. Use DIP switches 1 & 2 to adjust sensitivity.

Switch

1

2

PIR SENSITIvITY

OFF

OFF

100% (HIGH)

ON

OFF

85% (NORMAL)

OFF

ON

75% (MEDIUM )

ON

ON

60% (LOW)

Time Delay (Switches 3-7)

Use DIP switches 3 to 7 to adjust the time delay.

Switch

3

4

5

6

7

TIME DELAY

ON ON ON ON ON 15

seconds

OFF

ON

ON

ON

ON

5 minutes

OFF

OFF

ON

ON

ON

10 minutes

OFF OFF OFF ON ON 15

minutes

OFF OFF OFF OFF ON 20

minutes

OFF OFF OFF OFF OFF 30

minutes

PIR Override (Switches 8-10)

Overrides can disable control features of the PSHB120277Lx power module. The table below describes the override

functions of each PSHB120277Lx model.

IMPORTANT START-UP INFORMATION

A 60-second start-up period occurs during initial installation and after a power failure of 5 minutes or more. After

applying power to the sensor wait at least 60 seconds for the sensor to begin detecting occupancy and the load to

turn ON. It may turn ON during the start-up period, depending on the state of the relay when power was off.
• If the sensor detects occupancy during the start-up, when the load turns ON it stays ON as long as the sensor

continues to detect motion, plus the Time Delay.

• If no occupancy is detected during the 60-second start-up, the load may come on anyway during the start-up.

If no occupancy is detected by the time the start-up is complete, the relay opens and the load turns OFF.

MODEL/SWITCH #

8

9

10

FUNCTIONALITY

LOAD EFFECT

PSHB120277Lx

PIR sensor, 1 load relay

OFF

N/A

N/A

Occupancy control enabled

Controlled by Occupancy

ON

N/A

N/A

Override PIR

Load always ON

TROUBLESHOOTINg

If you suspect improper operation, review the Start-Up information. After start-up, the sensor will open or close the

relay to correspond to the occupancy status of the area. When power to the sensor is lost, the relay(s) close, turning

on the load if the load still has power.
To quickly test the unit, set the time delay to minimum. Wait for the start-up period to end. Move out of the sensor’s

view. Lights should turn OFF after 15 seconds. Move into the sensor’s view. The sensor’s Red LED should blink and

the lights should turn ON.
Red LED on power module does not blink:
Check sensor wire connections. Verify the neutral wire is tightly secured.

Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least one minute, then
a) Turn OFF power to the sensor.
b) The relay(s) will close.
c) Turn ON power to the sensor.
d) The load should come ON. If not, continue with step 2.
2. Check power connections to the light fixture.
3. Check all sensor wire connections. Verify the load wire is tightly secured.

CAUTION

Turn power off at the circuit breaker before installing

sensor.

AvERTISSEMENT

Coupez l’alimentation du disjoncteur avant

d’installer le détecteur.

PRECAUCIÓN

Desconecte la alimentación del disyuntor antes de

instalar el sensor.

SPECIFICATIONS

Voltages .............................................120/277VAC, 60Hz
Load Requirements
@ 120VAC, 60Hz ...........0-800W ballast or tungsten
@ 277VAC, 60Hz ............................0-1200W ballast
@

120VAC .......................................................1/6 hp

LENS

Hallway L1 ........ 40 ft. mounting height, 60 ft. x 20 ft.

L2 ..................20 ft. mounting height, 40 ft. diameter

L3 ..................40 ft. mounting height, 60 ft. diameter

SPÉCIFICATIONS

Voltages .........................................120/277 V c.a., 60 Hz
Conditions de charge

à 120 V c.a., 60 Hz ........0-800 W ballast ou tungstène
à 277 V c.a., 60 Hz ........................... 0-1200 W Ballast
à 120 V c.a. .........................................................1/6 hp

LENTILLE

L1 pour couloir ....... Hauteur de montage de 12,19 m,

18,28 m x 6,09 m.

L2 ............................. Hauteur de montage de 6,09 m,

diamètre de 12,19 m.

L3 ...........................Hauteur de montage de 12,19 m,

diamètre de 18,28 m.

ESPECIFICACIONES

Voltajes ...........................................120/277 V CA, 60 Hz
Requerimientos de carga

A 120 V CA, 60 Hz .......0 a 800 W balasto o tungsteno
A 277 V CA, 60 Hz ......................Balasto de 0-1200 W
A 120 V CA..........................................................1/6 hp

LENTE

Hallway L1 ...... Altura de montaje de 12 m (40 pies),

18 m x 6 m (60 pies x 20 pies)

L2 ..................... Altura de montaje de 6 m (20 pies),

diámetro de 12 m (40 pies)

L3 ................... Altura de montaje de 12 m (40 pies),

diámetro de 18 m (60 pies)

PSHB120277L2

PSHB120277L1

PSHB120277L3

Ceiling

30

20

10

0

10

20

30

0

10

20

30

40

Coverage Side View

40

30

20

10

0

10

20

30

40

0

20

10

10

20

20 ft

Coverage Top View

Ceiling

Side View

Top View L1

0 3 6

12

27

34

3

6

12

27

34

20

20

0

10

20

30

40

Coverage Side View

0 3 6

12

27 34

3

6

12

27

34

20

20

0

3

6

3

6

12

27

34

12

27

34

20

20

68 ft

Coverage Top View

0

6

6 3

3

Ceiling

Side View

Top View L3

0

3

9

6

3

6

9

12

12

10

20

0

15

Ceiling

Coverage Side View

5

15

18

20

15

18

20

Coverage Top View

20

10

0

10

20

0

20

10

10

20

40 ft

Ceiling

Side View

Top View L2

120/277VAC Wiring

Hot

Neutral

Load

Black

White

Red

PSHB120277Lx

Advertising
This manual is related to the following products: