Usage of the current loop interface, Active output to passive input, Passive output to active input – Meinberg DCF77C51 User Manual

Page 18

Advertising
background image

18

Usage of the Current Loop Interface

The current loop interface can be wired to work in one of two modes: active output
drives passive input, or passive output to active input.

Active Output to Passive Input

If the clock's current loop output shall be wired to operate as active output, a
connection from the pin labeled +pass_out to Vcc (+5V) must be provided. The pin
labeled -act_out is pulled down to the auxiliary -15V supply, which must be made
available by the user.

active current loop output with auxiliary -15V supply

If an external -15V supply is not available, the -act_out signal can be connected
directly to GND, as shown below:

active current loop output without auxiliary -15V supply

Advertising