Page 8

Advertising
background image

Page 8 of 19

MW38-DV Modular Fireplace

P/N XG0112

2' min.

Storm collar

Support ring

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Installation

Installation Of Vertical Vent DV

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 3' (three feet) from a parapet wall.

Maximum vent height is 35 feet above fireplace.
Note: Flame characteristics will change if the maximum vent
height is used.

Minimum clearances 1" from vent to all combustible materials
must be maintained.

Figure 13. Straight, vertical venting using required MXT-10 adaptor.

A maximum of two offsets with 90° bends may be made and shall not
exceed total length of 25% of the vertical vent height, when measured
center to center of piping.

Example: Typical vent installation.

20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed

This venting configuration meets requirements.

A - Termination

MVTK-1

B - Flex sections

MFL-1 (12" section)

MFL-2 (24" section)

MFL-3 (36" section)

MFL-4 (48" section)

C - Solid sections

MEXT-1 (12" section)

MEXT-2 (24" section)

MEXT-3 (36" section)

MEXT-4 (48" section)

MEXT-6 (72" Section)

D - Support Ring & Plate

MSPXT-8 (7" dia.)

E - Firestop

FS-7 (7" dia.)

F - Roof Flashing

MRF-7 (1/12 - 7/12 pitch)

MRF-12 (7/12 - 12/12 pt.)

MRF-16 (12/12 - 16/12 pt.)

Figure 14b. Vertical venting with 2 offsets.

Figure 14a. Vertical venting with 1 offset.

2' min.

2'

Storm collar

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support straps or
support plate & ring

Firestop

Firestop

Firestop

Support plate
& ring

35' max.

35' max.

Top Vent

Storm collar

Support ring

MEXT
Solid Section

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Firestop

2' min.

MXT-10

Adaptor

MEXT

Flue

Collar

35' max.