LS Installation Manual | 28

Mini SAM-e Pressurized without External Separator

Strainer

Manual Shut-Off
Valve (By Others)

Steam Main

1” Air Gap

Drain

Steam from top of main

6” min.

Return to non-pressurized
condensate return main

Pressurized condensate
return main

• Max steam pressure of 15 psig when no separator is used.
• Steam components in grey are provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.

When pressurized steam enters the SAM-e, the pressure drops down to almost atmospheric
pressure. Therefore, it must be drained atmospherically, and the use of a condensate pump
(rated for 212ºF) must be used to raise the condensate to a higher elevation.