Nortec GS Series User Manual

Page 59

Advertising
background image

GS Series Installation | 56

HUMIDIFIER
Model

: GSTC 600

Capacity

: 600 lb/hr

Multi Mode

: StandAlone

REG Mode

: Demand

Software V

: 1.07

Esc

Humidifier Information
Displays humidifier information and settings, including the
model name and output, the control signal type and the
software version.

Note: The Multi Mode indicates if the humidifier is
operating alone (StandAlone) or if is linked to other units
(Master or Slave). The REG mode indicates the control type,
either humidistat (Demand) or Transducer (RH).

BURNERS
Burners

: 6

Active

: 4

Capacity

: 600 lb/hr

Total O/P

: 305 lb/hr

Lead

: 1

Disabled

: -----X

Esc

Burner Information
Displays burner information. The lead burner is the first
burner to ignite for the present cycle. If burners are
disabled, they will be denoted by an X.

Note: In this view, burner 6 is disabled (denoted by X).

TANK STATUS
Fill Valve

: Off

Drain Pump

: Off

Float Levl

: 5

Run Time

: 12 hr

Serv. Time

: 500hr

Serv. Due

: 425hr

Esc

Tank Status
Displays information about the tank, operating time and
service time. The run time is the total operating time. The
service time indicates the fixed service interval length. The
service due time is the time remaining until service is
required.

Note: The service interval can be set in the Service Level.

SENSOR INPUTS
Sec. Loop

: Closed

OT Sensors

: Closed

Tank Temp

: Closed

Esc

Sensor Status
The SENSOR INPUTS screen displays the current status of
the Security Loop, the Over Temperature Sensors and the
Tank Temperature Sensor.

Note: The Security Loop and the Over Temperature
Sensors must be Closed for the humidifier to operate.

FEATURES LIST
Idle Mode

: Idle Drain

FTBD

: On

Time Prop.

: On

BD rate

: 25

Drain Cool

: Smart

Float Ck

: On

Esc

Features Information
Displays information of the User Settings including the idle
mode, the Full Tank Blow Down status, the Time
Proportioning status, the Blow Down rate percentage, the
Drain Cool mode and the Float Check status.

Note: See User Defined Settings to change these
parameters.

Advertising