Troubleshooting, Specification – Obvius A8923-4 User Manual

Page 2

Advertising
background image

Supported Modbus commands:
0x03 Read Holding Registors
0x06 Preset Single Register
0x11 Report Slave ID
All other Modbus commands return "Illegal Function" . The Status Register is the only register that is read/write.
Device ID = 50
Device name = "Obvius 4A4P-M2"

* Status Register (40013)

* Pulse State Register (40017)

Bits 0-3 Analog input type. bit 0 is Analog 1

0=4-20mA, 1=0-10V (read/write)

Bits 4-7 Analog overcurrent/voltage. bit 4 is Analog 1

0=Ok, 1=Alarm (read-only)

Bits 8-11 Analog broken 4-20mA wire. bit 8 is Analog 1

0=Ok, 1=Alarm (read-only)

Bit 12

Debounce feature slows down the pulse scan rate for mechanical relays
0=250Hz Max, 1=20Hz Max (read/write)

Bit 13

1 = resets min/max/average to current value (read/write)

Bit 14

bit is unused. Always 0

Bit 15

1 = set learn mode (read/write)

Bit 0

Pulse 1 status
0 = contacts open, 1 = contacts closed

Bit 1

Pulse 2 status
0 = contacts open, 1 = contacts closed

Bit 2

Pulse 3 status
0 = contacts open, 1 = contacts closed

Bit 3

Pulse 4 status
0 = contacts open, 1 = contacts closed

bits 4-15 Unused

The Obvius A8923-4 ships from the Factory configured for 0-10V. Press the Learn button if 4-20mA products are used.

When changing a single bit in the status register: First read the register from the IO module, next, set or clear the bit as needed and then write
the register value back to the IO module. Simply writing 0x20 to set the pulse input debounce feature will also force all analog inputs into 4-
20mA mode.

Troubleshooting

Power LED is not on:

Ensure 24VDC is present and polarity is correct.

Data LEDs do not blink:

Check network wiring, address selection. Verify master Modbus controller is functioning.

Pulse LEDs do not blink: Verify pulse inputs are dry contact or opto-isolator wired with correct polarity.
Analog values inaccurate: Verify analog devices are wired correctly. Press LEARN button to re-configure.

Verify Modbus master is configured to scale sensor outputs properly.
Check sensor output range. Make sure Modbus master is configured with correct scaling.

No output from unit:

Check network wiring, address selection. Verify Modbus master device is configured to read correct points.

Specification

Inputs
Power

24vdc, 50mA, + converter powered analog devices

Analog

4-20mA or 0-10v auto-detected (ranges and units set in master device)
0-10v Input impedance = 10k ohms
4-20mA Input Impedance = 250 ohms
Scan Rate 250mS (1/4 second)

Pulse

Dry contact, 250Hz max. (user selectable to 20Hz max)
input impedance 500 ohms max.

Accuracy

+/- 0.25% F.S. (Analog Input)

Output
Hardware

RS-485, 2-wire , non-isolated

Protocol

Modbus RTU Protocol, 9600baud

Latency

5mS

Configuration
Address

6-position DIP switch, 63 addresses

Analog Input

Auto-detecting 0-10v or 4-20mA (ranges and units set in master device)

General
Dimensions

4-module, 70mm x 86mm x 58mm(h)

Material

Base part: Black Noryl UL94-V0; PCB material: FR-4

Mounting

Compatible with M36 DIN-RAIL (EN50022)

Operating Environment 0 to 50 degrees C, 0 to 95%RH non-condensing

3300 NW 211

th

Terrace, Hillsboro, OR 97124, Ph: +1-503-601-2099

Date: Jun 21, 2010

Copyright © 2001-2010 Obvius, All rights reserved.

[email protected]